EasyManua.ls Logo

Siemens FM 458-1 DP - Page 45

Siemens FM 458-1 DP
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication blocks
Function Blocks - FM 458-1 DP 2-33
Edition 12.2004
The block saves the configured configuration data in the admin. area of
the COMBOARD. It executes this once after run-up and user-controlled
in the RUN mode. In the RUN mode, it outputs diagnostics data from the
COMBOARD at its outputs.
New configuration data can be transferred online to COMBOARD with a
positive edge at input SET.
CTR Configured name of the "righthand" adjacent module (initialization connection). The
following data can be entered:
CTR = 0 if an adjacent module was not configured
CTR=<module name> or
CTR=<module name>.<connector> if an adjacent board is configured.
(default value: - )
SET The configuration data is transferred online to the COMBOARD with a rising
edge at this input.
(Default value: 0)
MAA The station number should be assigned depending on the particular protocol
(e.g. USS: 0..30, PROFIBUS DP: 3..125).
(Default value: 0)
P01...P28 Max. 28 additional COMBOARD-specific configuration parameters.
(Default value: 0)
QTS Block status:
QTS = 1: Block is operational.
QTS = 0: The block is disabled with an error output at YTS
(Default value: 0)
YTS Status display, possible values
- 0: OK status
- 7CB3: T400 operates as TECHBOARD and a BASEBOARD is available
Additional values, refer to: D7-SYS Online Help "Help on events" (press key F1 in the CFC
and call-up the topic "Help on events" under "CFC for SIMADYN D".)
(Default value: 0)
D01...D28 Max. 28 words of diagnostics data of the COMBOARD
(Default value: 0)
Mode of operation
I/O

Table of Contents

Related product manuals