EasyManua.ls Logo

Siemens FM 458-1 DP - Page 46

Siemens FM 458-1 DP
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication blocks
2-34 Function Blocks - FM 458-1 DP
Edition 12.2004
The "CB-Param" and "SCB-Param" columns establish the assignment to
the COMBOARD User Manuals.
Input CB-Param
new/old
CB1:
DP
CBP:
DP
CBP2:
DP
CBP2:
USS
CB2:
CAN
MAA
P918 Bus address Bus address Bus address Bus address Bus address
P01
P711/
P696
(not used) Diagnostic
selection
Diagnostic
selection
- PKW task
P02
P712/
P697
PPO-Typ PPO-Typ PPO-Typ - PZD
receive
P03
P713/
P698
(END) (END) Protocol selection:
0: Profibus-DP
2: USS
PZD send
P04
P714/
P699
SIMATIC OP
writes in:
0: EEPROM
1. RAM
- PZD
send length
P05
P715/
P700
Slave to slave
data transfer
failed:
0: Error
1: Warning
- PZD
send rate
P06
P716/
P701
(END) - PZD
receive
Broadcast
P07
P717/
P702
- PZD
receive
Multicast
P08
P718/
P703
Baud rate
6 = 9,6
kBaud
7 = 19,2
kBaud
8 = 38,4
kBaud
PZD
receiver
cross
P09
P719/
P704
PKW: 0:no,
127:yes,
3:one word,
4:one D word
PKW task
Broadcast
P10
P720/
P705
PZD:
No. of words
Baud rate
P11
P706.1 (END) CAN layer
P12
P706.2 Bus timing
P13
P706.3 (END)
P14
P706.4
...
P28
Significance of the
configuring input
for several
COMBOARDs

Table of Contents

Related product manuals