9 Technical data
Supply
Operating voltage DC24V
Standby power consumption 95mA @24V
Built-in power consumption, supply via
MoNetBus or AUX power
Max. 380mA @ 24V
Power consumption via PoE Max. 185mA @ 24V
Ethernet interfaces
Sockets 4x RJ45, 10/100Mbit/s
Length of line ● P4, P5 'Local', limited to same
housing but must be min. 2m
● P2, P3 'Field', limited to same room
but must be min. 2m, max. 6m
Connectors
External supply input 4-pin plug-in terminal
Fault terminal 4-pin plug-in terminal
● Fault output 'F1', 'F2' Dry contact relay (common)
Switching current max. 1A, resistive
Switching voltage max. DC30V
MoNetBus 22-pin flat-cable connector
External Ethernet connections 'P2', 'P3' ● Additional voltage surge protection
● Increased EMC protection
● Ground fault supervision
Circuits ● All connections are power limited
● All connections – except local and
MoNet connections – are supervised
Module connections
(optional)
Ethernet module (electric) VN2001 RJ45 connection (TP), cable length max.
330ft/100m
Ethernet module (MM) VN2002 LC connector, multi-mode fiber optic
● Fiber length 62.5/125°µm:
13123ft/4km with an 11dB loss
1
● Fiber length 50/125°µm: 6561ft/2km
with a 7.5dB loss
1
Ethernet module (SM) VN2003 LC connector, single-mode fiber optic:
● Fiber length 9/125°µm:
131233ft/40km with a 29dB loss
1
Mechanical data
Dimensions (W x H x D), with cover,
without optional modules
165 x 121 x 43mm
Weight 560g/1.2lbs
Ambient conditions
For indoor use in dry rooms only
Operating temperature 120+/-3°F to 32+/-3°F
Rel. humidity during operation 93+/-2% at a temperature of 90+/-3°F
Protection category IP30
1
The length is a guide value dependent upon the loss of the cable used, the loss of the
connector types used, and the transmission losses that are present. The
corresponding values must be taken from the respective data sheets.
Technical data
9
A6V10407862_e_en_-- 29 | 32