5 Operation
5.1 ALARM Procedure
If your fire detection system does not have delayed alarm transmission ('AVC'), the –
'Fire Department in' 'mm:ss' variant doesn't apply to step 2 (see Procedure in the
event of alarm).
Procedure in the event of alarm
Step Action/Condition Consequence/Status
1
Press <Acknowledge> on the Person Machine
Interface
'AVC' starts count-down t2 to investigate the 'ALARM'
source
2 Read top line
on display
–'Fire Department requested' 'ALARM' is transmitted to the fire department
–'Fire Department in' 'mm:ss' 'ALARM' is transmitted to the fire department in
'mm:ss'
Remaining time is shown as
Count-down
–'Call Fire Department !'
When:
● Remote transmission switched off
● Remote transmission blocked or defective
● No remote transmission available
Fire department must be called by phone!
No automatic transmission to fire department
3
Read off
fire location
in display
4 Go to the fire location
5 Decide:
MAJOR INCIDENT or minor incident
Condition MAJOR INCIDENT Minor incident
Fire department has been
called
Save people
Guide the fire department to the fire
location
Fight the fire
Try to prevent the fire department
from being deployed
Press <Reset>
'Fire Department in' 'mm:ss'
Count-down runs
Activate 'Manual pull station'
immediately
Press <Reset>
'Call Fire Department !'
No automatic transmission to
the fire department
Call the fire department on the phone!
Press <Reset>
To reset, the key switch must be activated.
The room may have to be vented before a reset is possible.
Elements which cannot be reset can be temporarily bypassed on the control panel.