Circuit
Breaker
Positions
Circuit
Breaker
Cell
Preparation
The
circuit
breaker
cell
contains
the
positioning
,
interlocking
and
operating
devices
described
below
and
shown
in
Figures
35
and
37
.
These
devices
must
be
checked
for
placement
and
freedom
of
operation
.
A
WARNING
Hazardous
voltages
.
Can
cause
death
,
serious
injury
and
property
damage
.
Do
not
insert
a
circuit
breaker
into
a
cell
intended
for
a
circuit
breaker
with
ratings
above
those
of
the
circuit
breaker
being
inserted
.
Verify
that
circuit
breakers
and
cubicles
have
appropriate
ratings
and
properly
located
interference
blocking
plates
and
angles
before
attempting
to
insert
a
circuit
breaker
.
Circuit
Breaker
Racking
Mechanism
The
circuit
breaker
racking
mechanism
is
centered
below
the
circuit
breaker
.
It
functions
in
conjunction
with
the
trip
-
free
interlock
on
the
circuit
breaker
,
to
hold
the
circuit
breaker
trip
-
free
between
positions
.
Three
positions
are
provided
:
DISCONNECT
,
TEST
,
and
CONNECT
.
The
interlock
will
allow
a
2000
A
or
3000
A
circuit
breaker
to
enter
a
1200
A
cell
,
provided
the
voltage
,
interrupting
,
and
continuous
current
ratings
equal
or
exceed
the
ratings
of
the
cell
.
The
coordinating
interference
plate
on
the
circuit
breaker
is
shown
in
Figure
36
.
m
BUS
M
QJ
i
*
[
G
X
m
Qh
HI
3
A
t
id
E
m
[
£
m
A
.
Interference
blocking
plate
(
rating
interlock
)
B
.
Racking
mechanism
C
.
Ground
bar
D
.
Guide
rails
E
.
Trip
free
and
racking
interlock
padlock
provisions
F
.
MOC
switch
operator
G
.
MOC
switch
terminals
H
.
TOC
switch
terminals
I
.
Shutter
operating
linkage
J
.
Shutter
(
behind
barrier
)
K
.
CT
barrier
L
Secondary
disconnect
Figure
35
.
Circuit
Breaker
Compartment
(
MOC
/
TOC
Switch
Cover
Removed
for
Photo
)
Interference
Blocking
Plate
(
Rating
Interlock
)
This
plate
is
mounted
vertically
on
the
bottom
of
the
cell
to
allow
only
the
properly
rated
circuit
breaker
into
the
designated
cell
(
e
.
g
.
,
a
1200
A
circuit
breaker
to
enter
a
1200
A
cell
,
or
a
2000
A
circuit
breaker
to
enter
a
2000
A
cell
)
,
depending
on
the
voltage
,
interrupting
,
and
continuous
current
ratings
.
Normally
the
cubicle
and
circuit
breaker
rating
plate
combinations
will
be
identical
.
Figure
36
,
interlocks
on
Bottom
of
Circuit
Breaker
Secondary
Disconnect
The
secondary
disconnect
contains
all
the
electrical
control
circuit
connections
for
the
circuit
breaker
.
It
mates
with
the
secondary
disconnect
block
on
the
circuit
breaker
.
The
circuit
breaker
contacts
slide
against
the
cell
contact
strips
.
The
secondary
contacts
are
automatically
mated
in
the
TEST
and
CONNECT
positions
.
38
Courtesy of NationalSwitchgear.com