EasyManua.ls Logo

Siemens GM-SG

Siemens GM-SG
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Circuit
Breaker
Positions
Racking
from
CONNECT
to
TEST
or
DISCONNECT
Position
1
.
This
procedure
is
essentially
the
same
as
racking
to
connected
position
procedure
except
the
rotation
is
counterclockwise
.
2
.
Check
that
the
circuit
breaker
is
open
.
3
.
Close
instrument
door
.
4
.
Insert
racking
crank
(
see
"
Racking
Crank
Engagement
Procedure
"
)
and
rotate
counterclockwise
about
54
turns
to
a
positive
stop
and
the
position
indicator
indicates
"
D
"
for
DISCONNECT
position
.
The
intermediate
TEST
position
is
indicated
by
"
T
"
.
A
DANGER
A
.
Hazardous
voltages
.
Will
cause
death
or
serious
injury
.
De
energize
and
ground
the
equipment
before
checking
contact
penetration
.
Figure
45
.
Racking
Mechanism
shown
in
DISCONNECT
position
.
The
circuit
breaker
racking
method
has
been
designed
to
be
used
with
the
circuit
breaker
compartment
door
either
open
or
closed
;
however
,
it
is
recommended
that
the
door
be
closed
and
securely
latched
during
racking
.
Moving
the
circuit
breaker
between
the
CONNECT
and
TEST
or
DISCONNECT
positions
with
the
door
closed
provides
additional
protection
to
the
operator
and
is
the
recommended
procedure
.
Contact
Penetration
Make
certain
all
electrical
connections
to
both
the
line
/
load
and
bus
disconnects
are
de
-
energized
and
locked
out
.
This
can
be
verified
by
blocking
the
shutters
open
and
using
a
hot
stick
potential
device
to
double
-
check
that
all
disconnects
are
de
-
energized
.
Rack
the
circuit
breaker
completely
into
the
CONNECT
position
and
then
withdraw
it
from
the
cell
.
Check
that
the
contact
wipe
is
about
3
/
8
"
(
10
mm
)
on
the
cell
primary
disconnects
,
for
all
circuit
breaker
ratings
.
Racking
from
DISCONNECT
to
CONNECT
Position
1
.
Check
that
the
racking
position
indicator
shows
"
D
"
for
DISCONNECT
position
.
2
.
Check
that
the
circuit
breaker
is
fully
pushed
into
the
cell
to
the
DISCONNECT
position
.
3
.
Check
that
the
circuit
breaker
is
OPEN
.
4
.
Secondary
disconnects
will
automatically
connect
as
the
circuit
breaker
moves
to
the
TEST
and
CONNECT
position
.
5
.
Close
circuit
breaker
compartment
door
.
6
.
Insert
racking
crank
through
round
opening
at
bottom
of
door
and
onto
the
racking
screw
(
see
"
Racking
Crank
Engagement
Procedure
"
)
.
7
.
Push
the
racking
crank
forward
to
move
the
closed
circuit
breaker
racking
interlock
slide
back
which
will
allow
the
socket
to
engage
the
square
head
on
the
racking
screw
.
Do
not
force
slide
as
it
is
interlocked
to
prevent
sliding
forward
when
the
circuit
breaker
is
closed
.
8
.
Rotate
the
racking
crank
clockwise
about
54
turns
until
a
positive
stop
is
felt
and
the
position
indicated
shows
"
C
"
for
the
CONNECT
position
.
The
indicator
will
show
"
T
"
when
the
circuit
breaker
is
in
TEST
position
.
Closed
Circuit
Breaker
Racking
Interlock
The
closed
circuit
breaker
racking
interlock
is
designed
to
prevent
a
circuit
breaker
from
being
racked
from
TEST
to
CONNECT
and
vice
-
versa
with
the
primary
contacts
closed
.
Only
an
open
circuit
breaker
is
to
be
moved
between
these
positions
.
Refer
to
Figure
47
.
The
trip
free
interlock
slide
has
angle
-
shaped
members
(
Figure
47
,
item
60
)
that
project
from
the
right
side
of
the
racking
mechanism
and
engage
an
interlock
member
from
the
circuit
breaker
.
The
circuit
breaker
interlock
extends
down
to
prevent
movement
of
the
trip
free
interlock
slide
with
the
circuit
breaker
closed
.
When
engaged
,
the
racking
screw
is
not
accessible
to
the
racking
crank
until
the
circuit
breaker
has
been
opened
.
Note
:
Racking
handle
must
be
removed
,
allowing
the
interlock
slides
to
return
to
their
initial
position
.
The
circuit
breaker
may
now
be
closed
mechanically
or
electrically
.
43
Courtesy of NationalSwitchgear.com

Related product manuals