Installation
contact
by
drawing
down
anchoring
bolts
as
such
drastic
means
will
distort
cubicles
.
6
.
Add
clamp
washers
and
nuts
to
anchor
bolts
and
tighten
securely
.
7
.
Check
all
circuit
breaker
compartments
for
free
movement
of
the
shutters
.
8
.
Move
the
next
group
into
position
.
The
front
edge
of
the
cubicle
base
should
be
in
line
with
those
of
the
previously
installed
group
.
This
will
insure
a
good
fit
with
the
aisle
floor
plates
.
Make
certain
that
the
end
of
the
group
being
installed
is
tightly
against
the
previously
installed
group
.
Repeat
steps
5
,
6
,
and
7
and
install
all
shipping
split
hardware
.
Assembly
of
Common
-
Aisle
Shelter
-
Clad
Switchgear
Figure
14
illustrates
the
assembly
of
common
-
aisle
Shelter
-
Clad
switchgear
,
and
Table
3
lists
the
standard
components
supplied
.
The
item
numbers
in
the
table
are
used
in
all
instructions
pertaining
to
this
procedure
.
Assemble
as
follows
:
1
.
Install
all
floor
plates
.
2
.
Caulk
at
joints
.
3
.
Raise
door
assemblies
into
place
.
Bolt
doors
to
side
plates
of
cubicles
.
Note
:
Place
lift
truck
(
if
supplied
)
for
upper
cell
circuit
breakers
inside
the
aisle
enclosure
before
installation
of
the
last
door
assembly
to
the
enclosure
.
The
lift
truck
is
wider
and
higher
than
the
hinged
aisle
door
opening
,
which
prevents
convenient
entrance
of
the
lift
truck
if
the
door
assemblies
are
in
place
.
Assembly
of
Single
-
Aisle
Shelter
-
Clad
Switchgear
Figure
13
illustrates
the
assembly
of
single
-
aisle
Shelter
-
Clad
switchgear
,
and
Table
2
lists
the
standard
components
supplied
.
The
item
numbers
in
the
table
are
used
in
all
instructions
pertaining
to
this
procedure
.
Assemble
as
follows
:
1
.
Temporarily
support
the
aisle
wall
assembly
in
its
permanent
position
as
shown
in
the
general
arrangement
drawing
.
2
.
Put
roof
covers
in
place
to
hold
top
of
aisle
wall
in
place
.
Do
not
tighten
hardware
.
3
.
Align
the
ends
of
the
aisle
wall
,
aisle
channel
and
switchgear
.
Place
floor
plate
in
position
between
the
switchgear
and
wall
.
Install
each
set
next
to
the
end
position
between
the
switchgear
and
the
wall
.
With
floor
plate
set
tightly
against
the
switchgear
floor
plates
,
bolt
floor
plates
in
position
.
Tighten
anchor
bolts
to
secure
channel
locations
.
4
.
With
roof
cover
hardware
loose
,
plumb
front
wall
and
tighten
attaching
hardware
.
5
.
Install
all
floor
plates
.
6
.
Caulk
aisle
walls
.
Set
door
assemblies
in
place
.
Bolt
the
door
to
the
aisle
wall
and
to
the
side
plate
of
the
cubicle
.
4
.
Mount
aisle
conduit
,
switches
,
receptacle
and
wire
to
the
junction
boxes
.
See
conduit
arrangement
.
5
.
Place
roof
decks
in
position
and
fasten
with
bolts
provided
.
6
.
Fasten
the
roof
decks
together
with
3
/
8
"
hardware
.
7
.
Set
channel
-
shaped
covers
over
the
joints
of
roof
decks
and
bolt
to
clips
welded
to
roof
with
retainer
nuts
.
8
.
Tighten
all
bolts
to
complete
assembly
.
9
.
Drill
cable
cover
to
suit
conduit
.
Bolt
the
cover
in
place
.
10
.
If
equipment
consists
of
more
than
one
shipping
group
,
caulk
each
vertical
shipping
split
at
the
back
of
the
switchgear
with
metal
filler
provided
.
Assembly
of
Single
-
Aisle
Shelter
-
Clad
Switchgear
with
Work
Space
Figure
15
illustrates
the
assembly
of
single
-
aisle
Shelter
-
Clad
switchgear
with
an
attached
Work
Space
area
,
and
Table
4
lists
the
standard
components
supplied
.
The
item
numbers
in
the
table
are
used
in
all
instructions
pertaining
to
this
procedure
.
Assemble
as
follows
:
1
.
Mount
aisle
end
plate
at
the
end
opposite
the
work
space
.
2
.
Move
aisle
wall
to
its
permanent
location
as
indicated
on
the
general
arrangement
drawing
.
3
.
Mount
the
end
plate
and
proceed
.
4
.
Put
the
work
space
floor
plate
base
in
position
as
indicated
.
5
.
Assemble
aisle
walls
.
See
general
arrangement
drawing
for
location
of
special
panels
for
fans
,
etc
.
Apply
caulking
at
the
joints
of
the
wall
sections
.
6
.
Bolt
work
space
rear
plates
(
item
56
)
together
,
in
a
manner
similar
to
the
aisle
wall
sections
,
and
then
bolt
to
the
switchgear
unit
.
Note
:
Place
lift
truck
(
if
supplied
)
for
upper
cell
circuit
breakers
inside
the
aisle
enclosure
before
installation
of
the
last
door
assembly
to
the
enclosure
.
The
lift
truck
is
wider
and
higher
than
the
hinged
aisle
door
opening
,
which
prevents
convenient
entrance
of
the
lift
truck
if
the
door
assemblies
are
in
place
.
7
.
Put
all
roof
covers
in
place
and
bolt
to
the
adjoining
roof
cover
with
3
/
8
"
hardware
.
8
.
Set
roof
channels
over
roof
cover
joints
.
Bolt
to
clips
welded
to
roof
with
retainer
nuts
.
9
.
Drill
cable
cover
to
suit
conduit
installation
.
Bolt
the
cover
in
place
.
10
.
Mount
aisle
conduit
,
switches
,
receptacle
and
wire
to
the
junction
boxes
.
See
conduit
arrangement
.
11
.
If
equipment
consists
of
more
than
one
shipping
group
,
caulk
each
vertical
shipping
split
at
the
back
of
the
switchgear
with
metal
filler
provided
.
15
Courtesy of NationalSwitchgear.com