Inspection
and
Testing
Placing
Equipment
into
Service
To
place
equipment
in
service
for
the
first
time
proceed
as
follows
:
1
.
Check
that
all
circuit
breakers
are
open
and
all
control
circuits
energized
.
2
.
Connect
primary
incoming
power
source
to
equipment
.
3
.
Check
all
instruments
,
relays
,
meters
,
etc
.
,
during
this
time
.
4
.
Connect
as
small
a
load
as
possible
and
observe
instruments
.
Note
:
Allow
several
minutes
before
connecting
additional
load
.
5
.
Gradually
connect
more
load
to
the
equipment
while
observing
instruments
until
the
full
load
is
connected
.
6
.
Check
for
signs
of
overheating
of
primary
and
secondary
circuits
and
satisfactory
operation
of
all
instruments
during
the
first
week
of
operation
.
46