Internal
Accessories
A
DANGER
*
Hazardous
Voltage
.
Will
cause
death
or
severe
injury
.
Turn
power
off
supplying
switchboard
or
panel
before
installing
.
A
Safety
Instructions
Circuit
Breaker
Preparation
A
.
Depress
trip
button
(
Figure
1
)
to
trip
circuit
breaker
prior
to
removing
cover
.
Before
attaching
accessory
unit
,
circuit
breaker
must
be
in
tripped
position
.
B
.
Remove
two
terminal
shield
screws
on
load
end
cover
(
1
)
,
load
end
cover
screws
(
5
or
9
)
(
2
)
and
,
if
breaker
is
mounted
,
also
remove
mounting
screws
(
not
shown
)
.
Remove
load
end
cover
only
(
3
)
.
Accessory
units
can
be
mounted
in
either
right
or
left
poles
of
the
circuit
breaker
,
except
types
with
an
"
FP
"
prefix
or
an
"
S
"
suffix
,
which
can
only
be
mounted
in
the
right
pole
.
f
Figure
1
Accessory
Mounting
Instructions
A
.
Feed
accessory
leads
down
and
through
5
/
16
x
1
/
2
"
elongated
opening
(
4
)
to
bring
leads
out
of
bottom
of
cir
-
cuit
breaker
(
Figure
3
)
.
NOTE
:
Leads
must
be
brought
out
in
the
same
order
as
they
exit
wire
retainer
of
accessory
case
.
B
.
Accessory
is
located
in
circuit
breaker
by
groove
(
5
)
,
bot
-
tom
side
of
accessory
.
Remove
protective
label
from
top
of
trip
unit
and
guide
actuator
(
9
)
into
opening
(
10
)
.
NOTE
:
On
shunt
trip
,
undervoltage
trip
and
auxiliary
switch
accessories
,
transfer
link
is
in
top
opening
and
transfer
link
slides
into
top
opening
of
trip
unit
.
Transfer
link
is
in
bottom
opening
of
Bell
Alarm
switch
and
slides
into
bottom
opening
of
the
trip
unit
.
Figure
2
f
Figure
3
26
Courtesy of NationalSwitchgear.com