Pressure
Wire
Connectors
A
DANGER
h
Hazardous
Voltage
.
Will
cause
death
or
severe
injury
.
Turn
power
off
supplying
switchboard
or
panel
before
installing
.
A
Safety
Instructions
General
Each
connector
kit
contains
a
solderless
connector
and
associ
-
ated
hardware
for
making
one
line
or
load
connection
.
Installation
NOTE
:
Trip
unit
must
be
installed
in
circuit
breaker
prior
to
mounting
load
end
connector
.
A
.
Tighten
mounting
screws
(
1
)
to
securely
attach
connector
.
See
table
for
torque
values
.
B
.
Tighten
set
screws
(
2
)
securely
to
prevent
overheating
of
conductor
and
connector
.
See
table
for
torque
values
.
Figure
1
Connector
Catalog
Numbers
Circuit
Breaker
Ampere
Rating
Connector
Wire
Range
Set
Screw
Torque
(
in
-
lbs
.
)
Mounting
Screw
Torque
(
in
-
lbs
.
)
For
Use
With
Frames
(
1
-
2
)
#
3
/
0
-
500
kcmil
(
Cu
)
(
1
-
2
)
#
4
/
0
-
500
kcmil
(
Al
)
200
-
600
300
132
JD
-
LD
300
TA
2
J
6500
250
-
600
(
1
)
#
500
-
750
kcmil
(
Al
)
(
1
)
#
500
-
600
kcmil
(
Cu
)
500
228
JD
-
LD
500
TA
1
L
6750
200
-
600
(
1
)
#
3
/
0
-
600
kcmil
(
Cu
)
500
228
JD
-
LD
TC
1
J
6600
(
1
-
2
)
#
3
/
0
-
500
kcmil
(
Cu
)
200
-
600
300
132
JD
-
LD
TC
2
J
6500
7
Courtesy of NationalSwitchgear.com