Siemens JXD2 - Electrical Check; Undervoltage Trip

Siemens JXD2
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Shunt
Trip
and
Undervoltage
Trip
Electrical
Check
Shunt
Trip
A
.
Reset
and
turn
circuit
breaker
ON
.
B
.
Attach
test
circuit
to
accessory
leads
.
When
the
test
volt
-
age
reaches
55
percent
or
more
of
the
rated
coil
voltage
,
the
circuit
breaker
should
trip
.
C
.
With
breaker
TRIPPED
or
OFF
,
check
to
make
sure
coil
cir
-
cuit
has
opened
.
Undervoltage
Trip
A
.
With
breaker
in
TRIPPED
position
,
connect
test
circuit
to
accessory
leads
.
Energize
undervoltage
trip
device
at
85
percent
of
the
marked
rated
voltage
of
the
coil
.
Reset
and
turn
breaker
handle
ON
.
B
.
Reduce
voltage
to
35
percent
of
rated
coil
voltage
.
Circuit
breaker
must
trip
.
Shunt
Undervoltage
Trip
Trip
rmm
Limit
Switch
Closed
When
Breaker
is
Closed
r
r
t
>
n
u
'
1
Customer
Supply
Customer
Supply
Electrical
Data
For
Shunt
Trip
Electrical
Data
For
Undervoltage
(
UV
)
Trip
® ©
Inrush
Current
At
Rated
Voltage
(
Amperes
)
Coil
Catalog
Number
Catalog
Number
Voltage
Sealed
-
In
Current
At
Rated
Voltage
(
Amperes
)
Coil
Voltage
60
Cycles
AC
1
UV
Trip
1
UV
Trip
Plus
12
S
19
JLD
6
S
17
JLD
6
S
18
JLD
6
S
01
JLD
6
S
02
JLD
6
S
03
JLD
6
S
15
JLD
6
S
04
JLD
6
S
06
JLD
6
Only
1
Aux
.
Sw
.
24
48
60
Cycles
AC
Consult
Sales
Office
120
120
U
01
JLD
62
A
U
02
JLD
62
A
U
03
JLD
62
A
U
16
JLD
64
A
U
06
JLD
64
A
U
01
JLD
6
U
02
JLD
6
U
03
JLD
6
U
16
JLD
6
U
06
JLD
6
U
08
JLD
6
208
208
Consult
Sales
Office
240
240
277
277
480
480
600
600
®
N
/
A
DC
DC
12
S
16
JLD
6
S
07
JLD
6
S
09
JLD
6
S
11
JLD
6
S
13
JLD
6
24
U
13
JLD
62
A
U
14
JLD
62
A
U
10
JLD
62
A
U
12
JLD
62
A
U
13
JLD
6
U
14
JLD
6
U
10
JLD
6
U
12
JLD
6
Consult
Sales
Office
24
Consult
Sales
Office
48
48
125
125
250
©
250
©
Resistor
to
be
mounted
externally
of
circuit
breaker
and
connected
by
installer
.
®
All
auxiliary
switch
ratings
are
the
same
as
auxiliary
switch
kit
A
01
FD
64
.
@
Kit
includes
a
30
k
ohm
,
25
watt
resistor
(
Clarostat
Cat
.
No
.
VP
-
25
-
K
or
equivalent
)
.
®
Kit
includes
a
2.5
k
ohm
,
25
watt
resistor
(
Clarostat
Cat
.
No
.
VP
-
25
-
K
or
equivalent
)
.
A
\
28
Courtesy of NationalSwitchgear.com