Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
130/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
SW Version SW version of burner control 0..65535 User --- x
SW Version 0..65535 User --- x
RatioControl Parameter settings for ratio control User x x
GasSettings Parameter settings for firing on gas Service x x
SpecialPosi-
tions
Setting the special actuator positions for firing on gas Service x x
HomePos Setting the home positions for firing on gas Service x x
HomePosGas Home position of fuel damper (gas) 0..90° Service x x
HomePosAir Home position of air damper (gas) 0..90° Service x x
HomePosAux1 Home position of auxiliary damper (gas) 0..90°
0..100 %
Service x x
HomePosAux2 Home position of auxiliary damper 2 0..90° Service x
HomePosAux3 Home position of auxiliary damper 3 0..90° Service x
HomePosVSD Home position of VSD 0..100 % Service x
PrepurgePos Setting the prepurge positions for firing on gas Service x x
PrepurgePosAir Prepurge position of air damper (gas) 0..90° Service 90° x x
Prepurge-
PosAux1
Prepurge position of auxiliary damper (gas) 0..90°
0..100 %
Service 90° x x
Prepurge-
PosAux2
Prepurge position of auxiliary damper 2 0..90° Service 90° x
Prepurge-
PosAux3
Prepurge position of auxiliary damper 3 0..90° Service 90° x
Prepurge-
PosVSD
Prepurge position of VSD 0..100 % Service 100 % x
IgnitionPos Setting the ignition positions for firing on gas Service x x
IgnitionPosGas Ignition position of fuel damper (gas) 0..90° Service invalid x x
IgnitionPosAir Ignition position of air damper (gas) 0..90° Service invalid x x
IgnitionPosAux Ignition position of auxiliary damper (gas) 0..90°
0..100 %
Service invalid x x
IgnitionPosAux2 Ignition position of auxiliary damper 2 0..90° Service invalid x
IgnitionPosAux3 Ignition position of auxiliary damper 3 0..90° Service invalid x
IgnitionPosVSD Ignition position of VSD 10..100 % Service invalid x
PostpurgePos Setting the postpurge positions for firing on gas Service x x
PostpurgePos-
Gas
Postpurge position of fuel damper (gas) 0..90° Service 15° x x
PostpurgePosAir Postpurge position of air damper (gas) 0..90° Service 15° x x