EasyManua.ls Logo

Siemens LMV51.000B2 - Connection to Superposed Systems; General Information and BACS Functions; Reading Ebus-Specific; Data

Siemens LMV51.000B2
299 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
7.2.2 Connection to superposed systems
(Refer to «Port for BACS»)
Communication with a BACS is accomplished via a data link and an external bus inter-
face with galvanic separation. That interface is to be connected to the COM2 port of the
AZL5… . The interface can be used for eBus or Modbus, depending on the configuration
of the AZL5...
Modbus
With this bus protocol, the AZL5... operates as a slave. The transmission mode used is
RTU (Remote Terminal Unit). For detailed information, refer to the document “Modbus
AZL5...“.
Standardized interfacing software is available on request.
Example
: Interconnection of Siemens Simatic S7 and LMV5... system
Use in industrial applications
Management level
Automation level
Sub station
Process control
Field level
Burner management system
Burner control, boiler control
DP/MODBus converter
CAN bus
LMV5... system
7550p20e/1003
eBus
The following functions can be provided:
Reading parameters and operating states
Hours run
Reading of start counter
Fuel consumption (LMV51.2..., LMV52...)
Operating display
Current type of fuel
Phase number
Input states (if available)
Output states including alarms (if available)
Actual value of temperature or pressure
Temperature or pressure setpoint
Current output
Final temperature or pressure setpoint
Contents of lockout and error storages
Identification (device identification, eBus software version)
Existence inquiry
Querying supported commands
Fault status message
General information
and BACS functions
Reading eBus-specific
data

Table of Contents

Related product manuals