Siemens LMV51.000B2 - Example 1 (Calculation of Test Time); Example 2 (Determination of Detectable Leakage Rate)

Siemens LMV51.000B2
299 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
164/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 8 Commissioning instructions for the LMV5... system 13.08.2004
P
G
= 30 mbar
P
W
= 15 mbar
P
atm
= 1013 mbar
V = 3 l
Q
Leck
= 50 l / h
Result: The test time to be set is 4 seconds
P
G
= 30 mbar
P
W
= 15 mbar
P
atm
= 1013 mbar
V = 3 l
t
Test
= 4 s
Result: The detected leakage rate is 40 l / h
Example 1 (calculation of
test time)
Example 2 (determination
of detectable leakage
rate)
(30 - 15) mbar 3 l 3600 s / h
t
Test
=
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯ = 3.2 s
1013 mbar 50 l / h
(30 - 15) mbar 3 l 3600 s / h
Q
Leck
= ⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯ = 40.0 l / h
1013 mbar 4 s