Siemens Building Technologies  Basic Documentation LMV5...  CC1P7550en 
HVAC Products  16 Addendum 1: List of fault status messages of LMV5... system  13.08.2004 
 
Error 
code 
Diagnostic 
code 
Device  Display  Meaning for the LMV5x system  Troubleshooting 
16  05  BU  Internal Fault Basic Unit  VSD curve is not fully defined  Check the curve to see if correct values have been entered 
for the VSD. Readjust the ratio curve, if required 
16  0A  BU  Internal Fault Basic Unit  Calculated P-part outside the permissible 
range 
Check to see if correct values have been entered for the 
controller parameters. Readjust O2 trim control, if required, 
or repeat the settings 
16  0B  BU  Internal Fault Basic Unit  Calculated I-part outside the permissible 
range 
Check to see if correct values have been entered for the 
controller parameters. Readjust O2 trim control, if required, 
or repeat the settings 
16  0C  BU  Internal Fault Basic Unit  Calculated system delay time outside the 
permissible range 
Check to see if correct values have been entered for the 
controller parameters. Readjust O2 trim control, if required, 
or repeat the settings 
16  0D  BU  Internal Fault Basic Unit  Calculated O2 setpoint outside the permis-
sible range 
Check to see if correct values have been entered for the O2
setpoints. Readjust O2 trim control, if required, or repeat 
the settings 
16  0E  BU  Internal Fault Basic Unit  Calculated O2 min. value outside the per-
missible range 
Check to see if correct values have been entered for the O2
min. values. Readjust O2 trim control, if required, or repeat 
the settings 
16  0F  BU  Internal Fault Basic Unit  Calculated O2 ratio value outside the per-
missible range 
Check to see if the correct values have been entered for the
O2 ratio values. Readjust O2 trim control, if required, or re-
peat the settings 
16  03  BU  Internal Fault Basic Unit  The load / point number predefined by the 
AZL… lies outside the permissible range 
*1) 
16  14  BU  Internal Fault Basic Unit  Calculated standardized value lies outside 
the permissible range 
Check if the correct values have been entered for the stan-
dardized values. Readjust O2 trim control, if required, or re-
peat the settings 
16  20  BU  Internal Fault Basic Unit  With hysteresis compensation: Permissible
target positioning range exceeded 
*1) 
16  21  BU  Internal Fault Basic Unit  The load / point number predefined by the 
AZL… lies outside the permissible range 
*1)