EasyManua.ls Logo

Siemens LOGO! 12/24RC - Technical Specifications: LOGO! 12...

Siemens LOGO! 12/24RC
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
199
LOGO! Manual
A5E00067781 01
A.5 Technical Specifications: LOGO! 12...
LOGO! 12RCL LOGO! 12/24RC
LOGO! 12/24RCo
Power supply
Input voltage 12 V DC 12/24 V DC
Permissible range 10.8 ... 15.6 V DC 10.8 ... 15.6 V DC
20.4 ... 28.8 V DC
Power consumption 10 ... 165 mA
(from 12 V DC)
10 ... 120 mA
(from 12/24 V DC)
Voltage failure bridging Typically 5 ms Typically 5 ms
Power loss 0.1 ... 2.0 W
(at 12 V DC)
0.1 ... 1.2 W
(at 12/24 V DC)
Clock buffering at 25 C Typically 80 h Typically 80 h
Accuracy of the real–time
clock
Max. 5 s a day Max. 5 s a day
Electrical isolation No No
Reverse polarity protection Yes Yes
Digital inputs
Number 12 8
Electrical isolation No No
Input voltage L+
Signal 0 < 4 V DC < 5 V DC
g
Signal 1 > 8 V DC > 8 V DC
Input current at
Signal 0 < 0.5 mA
> 1.5 mA
< 1.0 mA (I1...I6)
< 0,05 mA (I7, I8)
Signal 1
>
1
.
5
mA
,(,)
> 1.5 mA (I1...I6)
> 0,1 mA (I7, I8)
Delay time at
0 after 1 Typically 1.5 ms Typically 1.5 ms
1 after 0
yy
Typically 1.5 ms
yy
Typically 1.5 ms
Technical Specifications

Table of Contents