14 MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3
MM430 Specifications
Frame Size Dimensions Tightening torques for power terminals
C
B x H x T
mm
185 u 245 u 195
Nm 2,25
inch
7,28 u 9,65 u 7,68
lb
f
-ft 1,7
D
B x H x T
mm
275 u 520 u 245
Nm 10 (max.)
inch
10,82 u 20,47 u 9,65
lb
f
-ft 7,4 (max.)
E
B x H x T
mm
275 u 650 u 245
Nm 10 (max.)
inch
10,82 u 25,59 u 9,65
lb
f
-ft 7,4 (max.)
F
B x H x T
mm
350 u 850 mm u 320 (Height with filter 1150)
Nm 50
inch
13,78 u 33,46 u 12,60 (Height with filter 45,28)
lb
f
-ft 36,9
FX
B x H x T
mm
326 u 1400 u 356
Nm 25
inch
12,80 u 55,12 u 12,83
lb
f
-ft 18,4
GX
B x H x T
mm
326 u 1533 u 545
Nm 25
inch
12,80 u 60,35 u 21,46
lb
f
-ft 18,4
Input voltage range 3 AC 380 V … 480 V, ± 10 % (with built in Class A Filter)
Order No. 6SE6430- 2AD27
-5CA0
2AD31
-1CA0
2AD31
-5CA0
2AD31
-8DA0
2AD32
-2DA0
2AD33
-0DA0
Recommended Fuse
[A] 20 32 35 50 63 80
3NA 3807 3812 3814 3820 3822 3824
Fuses recommended for
UL applications
[A] 50 63 80
3NE * * * 1817-0 1818-0 1820-0
Input Cable Min.
[mm
] 2,5 4,0 6,0 10,0 10,0 16,0
[AWG] 14 12 10 8 8 6
Input Cable Max.
[mm
] 10,0 10,0 10,0 35,0 35,0 35,0
[AWG] 8 8 8 2 2 2
Output Cable Min.
[mm
] 2,5 4,0 6,0 10,0 10,0 16,0
[AWG] 14 12 10 8 8 6
Output Cable Max.
[mm
] 10,0 10,0 10,0 35,0 35,0 35,0
[AWG] 8 8 8 2 2 2
Order No. 6SE6430- 2AD33
-7EA0
2AD34
-5EA0
2AD35
-5FA0
2AD37
-5FA0
2AD38
-8FA0
Recommended Fuse
[A] 100 125 160 200 250
3NA 3830 3832 3836 3140 3144
Fuses recommended for
UL applications
[A] 100 125 160 200 250
3NE 1021-0 1022-0 1224-0 1225-0 1227-0
Input Cable Min.
[mm
] 25,0 25,0 35,0 70,0 70,0
[AWG] 3 3 2 2/0 2/0
Input Cable Max.
[mm
] 35,0 35,0 150,0 150,0 150,0
[AWG] 2 2 300 300 300
Output Cable Min.
[mm
] 25,0 25,0 50,0 70,0 95,0
[AWG] 3 3 1/0 2/0 4/0
Output Cable Max.
[mm
] 35,0 35,0 150,0 150,0 150,0
[AWG] 2 2 300 300 300
*UL listed fuses, such as those stated in the warnings on page 2 are required for use in America.
*UL-gelistete Sicherungen, wie in den Warnhinweisen auf Seite 2 angegeben, sind für den Einsatz in Amerika vorgeschrieben.
*Des fusibles homologués UL, tels que ceux mentionnés dans les avertissements à la page 2 sont requis pour une utilisation en Amérique.
*I fusibili omologati UL, come quelli indicati nelle avvertenze a pagina 2, sono richiesti per l'utilizzo sul territorio americano.
*Para uso en Norteamérica se requieren fusibles conformes a UL, como los que figuran en las advertencias de la página 2.