MICROMASTER 420/430/440
CANopen Option Module
Operating Instructions
Issue 01/05
User Documentation
6SE6400-5BC00-0BP0

Table of Contents

Other manuals for Siemens MICROMASTER 430

Questions and Answers

  • L
    Lucas WolfSep 18, 2025
    How to troubleshoot Siemens Control Unit Can Chip Passive Warning?
    • A
      Amy SaundersSep 18, 2025
      To troubleshoot a Can Chip Passive Warning in the Siemens Control Unit: * Check and correct, if required, the most significant digit of P2041.04 (baud rate) for every bus node. * Check the cable connection between bus nodes. * Check cable shielding. * Replace the CANopen module.
  • S
    Samuel ArellanoAug 25, 2025
    How to fix Siemens DC Drives motor that fails to run after changing parameters?
    • K
      kevin49Aug 25, 2025
      If your Siemens DC drive motor won't run after you've changed the parameters, try this: First, set P0010 = 30, then P0970 = 1, and press the P button to reset the inverter to its factory default parameter values. Alternatively, use a switch between terminals 5 and 9 on the control board. The drive should now run to the defined setpoint by analogue input.
  • M
    Michelle HarrisAug 27, 2025
    What to do if my Siemens Inverter displays F0002 OverVoltage?
    • K
      Kaitlyn HolmesAug 27, 2025
      If your Siemens Inverter is showing an F0002 OverVoltage error, it means the DC-link voltage (r0026) is exceeding the trip level (P2172). To fix this, verify that the supply voltage (P0210) is within the limits specified on the rating plate. Also, ensure the DC-link voltage controller is enabled (P1240) and properly parameterized. The ramp-down time (P1121) should match the inertia of the load, and the required braking power must be within specified limits.
  • C
    Christine SaundersAug 27, 2025
    What to do if my Siemens MICROMASTER 430 Inverter displays F0003 UnderVoltage?
    • A
      Ashley MataAug 27, 2025
      If your Siemens Inverter displays the error F0003 UnderVoltage, it indicates that the main supply has failed. To address this, check that the supply voltage (P0210) is within the limits indicated on the rating plate. Also, ensure that the supply is not susceptible to temporary failures or voltage reductions.
  • D
    David WilliamsonSep 22, 2025
    What to do if Siemens Control Unit data set changed, but failed to update parameter?
    • D
      Daryl SmithSep 22, 2025
      If the data set changed, but failed to update parameter accordingly in your Siemens Control Unit, repeat the change of dataset.
  • S
    Stephen MillerNov 24, 2025
    Why Siemens MICROMASTER 430 Inverter shows F0001 OverCurrent?
    • M
      Martin JonesNov 24, 2025
      The F0001 OverCurrent error on your Siemens Inverter can occur due to several reasons: * The motor power (P0307) doesn't match the inverter power (r0206). * Cable length limits are exceeded. * There are short-circuits or earth faults in the motor cable or motor. * Motor parameters don't match the motor in use. * The stator resistance (P0350) value is incorrect. * The motor is obstructed or overloaded. * The duty cycle is too demanding. * Motor power (P0307) exceeds inverter power capability (r0206). To resolve this, check that the motor power corresponds to the inverter power, ensure cable length limits are not exceeded, inspect the motor cable and motor for short-circuits or earth faults, verify that the motor parameters match the motor in use, confirm the stator resista...
  • K
    Kristina SinghSep 10, 2025
    What does F0022 Powerstack fault mean on a Siemens Inverter and how to fix it?
    • T
      tinawheelerSep 10, 2025
      The F0022 Powerstack fault on your Siemens Inverter is a hardware fault (P0947 = 22 and P0949 = 1) caused by events such as DC-link overcurrent, short circuit of chopper, earth fault, or I/O board not properly inserted. Check the I/O board to ensure it is fully pressed home.
  • E
    Emma BarnettSep 12, 2025
    What to do if Siemens Inverter motor fails to start when the ON command has been given?
    • T
      thomas29Sep 12, 2025
      If the motor fails to start when the ON command has been given to your Siemens Inverter, check that a valid ON signal is present. Also, verify that P0700 = 2 (for digital input control) or P0700 = 1 (for BOP-2 control). Finally, ensure that the setpoint is present (0 to 10V on Terminal 3) or that the setpoint has been entered into the correct parameter, depending upon the setpoint source (P1000).
  • B
    boyerkyleSep 4, 2025
    What does Siemens MICROMASTER 430 error F0051 Parameter EEPROM Fault mean?
    • A
      Angela SmithSep 4, 2025
      The F0051 Parameter EEPROM Fault on your Siemens Inverter indicates a read or write failure while saving a non-volatile parameter. To resolve this, try a factory reset and new parameterization. If the issue persists, consider changing the drive.
  • A
    Amber CalderonSep 2, 2025
    What does F0020 Mains Phase Missing mean on a Siemens MICROMASTER 430 Inverter and how to fix it?
    • A
      Aaron JohnsonSep 2, 2025
      If your Siemens Inverter displays the error F0020 Mains Phase Missing, check the input wiring of the mains phases.

Summary

Description

Technical Data

Module status LED, diagnostics, and baud rates supported.

Functionality of CANopen

Supports SDOs, PDOs, PDO mapping, communication profiles, and monitoring services.

General CAN;CANopen Definitions

CAN (Controller-Area-Network)

Features and characteristics of the CAN protocol: message-oriented, prioritization.

CANopen

Standardized application for distributed industrial automation systems based on CAN.

Data Transfer using CANopen

MICROMASTER Object Directory

Lists objects, index/subindex, description, data type, and default value for transfer.

CANopen Communication Services

Services for network management, communication monitoring, SDO, PDO, and emergency messages.

Connecting to CANopen

Installing the CANopen Module

Instructions for installing the module on different MICROMASTER sizes (A, B, C, D, E, F, FX, GX).

Bus Connection

Pin assignments, recommended bus cables, termination, and ground connection details.

Commissioning with CANopen

Important Parameters for First-Time Commissioning

Key parameters to check for initial system setup: Node ID, baud rate, telegram failure time.

Setting-up the PDOs

Configuring PDOs, mapping entries, and data transfer types using parameters.

Commissioning using a Commissioning (Start-Up) Tool

Assigning Process Data

Allocating purpose to PZD data using parameters P0700, P1000, P2050, and P2051.

Parameter Settings for the Modes

Overview of BICO connections for Velocity Mode and Profile Torque Mode.

Diagnostics and Troubleshooting

LED Display

Explanation of the combi LED states for module/network status and errors.

Alarms (Warnings and Faults)

Table of alarms, warnings, and faults displayed at the drive converter.

Attachment

Technical Data

Specifications for dimensions, mechanical strength, environmental conditions, and power.

List of Abbreviations

Glossary of abbreviations used throughout the document.

Siemens MICROMASTER 430 Specifications

General IconGeneral
Power Range7.5 kW to 250 kW
Voltage Range380V to 480V
Frequency Range0 Hz to 650 Hz
Protection ClassIP20
Input Frequency47 Hz to 63 Hz
Digital Inputs6
Cooling MethodForced-air cooling
CommunicationUSS
Protection FeaturesOvervoltage, undervoltage, overcurrent, short-circuit, ground fault, overtemperature
Analog Inputs2
Digital Outputs3
Analog Outputs2
Ambient Temperature-10°C to +50°C
Control TypeSensorless vector control