Information for the CANopen master  Issue 01/05 
  CANopen Option Module    Operating Instructions 
102  6SE6400-5BC00-0BP0 
5.8.2  Additional helpful commands for the profile torque mode 
Setting the baud rate: 
Write 500 into object 0x27DA sub 0 
T0 00:00:36,4500: 0x603  8-Data: 2b da 27 00 f4 01 00 00   
R0 00:00:38,2083: 0x583  8-Data: 60 da 27 00 00 00 00 00  
The new baud rate becomes active after the drive has restarted 
Setting the NodeID (CANopen node name): 
Write 4 for NodeID=4 into object 0x2396 sub 0 
T0 00:00:19,0341: 0x603  8-Data: 2f 96 23 00 04 00 00 00   
R0 00:00:19,0540: 0x583  8-Data: 60 96 23 00 00 00 00 00  
The new node name becomes active after the drive has restarted 
Save the CANopen parameters with "SAVE", object 0x1010: 
Write 0x65766173 into object 0x1010 sub 1 
T0 00:00:19,1443: 0x603  8-Data: 23 10 10 01 73 61 76 65    
R0 00:00:38,1658: 0x583  8-Data: 60 10 10 01 00 00 00 00 
Check the PDO mapping using MICROMASTER parameter P2041 (0x27F9*): 
The data apply to the mapping set above: 
 
Read FF FF from object 0x27F9 sub 0 
T0 00:02:52,5010: 0x604  8-Data: 40 f9 27 00 00 00 00 00      
R0 00:02:52,5160: 0x584  8-Data: 4b f9 27 00 ff ff 00 00 
 
Read 00 FF from object 0x27F9 sub 1: 
T0 00:02:52,5946: 0x604  8-Data: 40 f9 27 01 00 00 00 00   
R0 00:02:52,6144: 0x584  8-Data: 4b f9 27 01 ff 00 00 00 
 
Read 11 11 from object 0x27F9 sub 2: 
T0 00:02:52,6746: 0x604  8-Data: 40 f9 27 02 00 00 00 00   
R0 00:02:52,6962: 0x584  8-Data: 4b f9 27 02 11 11 00 00  
 
Read 41 41 from object 0x27F9 sub 3: 
T0 00:02:52,7545: 0x604  8-Data: 40 f9 27 03 00 00 00 00        
R0 00:02:52,7699: 0x584  8-Data: 4b f9 27 03 41 41 00 00