5.7.2 Additional helpful commands for the velocity mode
Setting the baud rate to 500 kbit/s:
Write 500 into object 0x27DA sub 0:
T0 00:00:36,4500: 0x603 8-Data: 2b da 27 00 f4 01 00 00
R0 00:00:38,2083: 0x583 8-Data: 60 da 27 00 00 00 00 00
The new baud rate becomes active after the drive is re-started
Changing the NodeID (CANopen node name):
Write 4 for NodeID=4 into object 0x2396 sub 0
T0 00:00:19,0341: 0x603 8-Data: 2f 96 23 00 04 00 00 00
R0 00:00:19,0540: 0x583 8-Data: 60 96 23 00 00 00 00 00
After the drive re-starts, the new NodeID becomes active
Save the CANopen parameter with "SAVE", object 0x1010:
Write 0x65766173 into object 0x1010 sub 1
T0 00:00:19,1443: 0x603 8-Data: 23 10 10 01 73 61 76 65
R0 00:00:38,1658: 0x583 8-Data: 60 10 10 01 00 00 00 00
Check the PDO mapping using MICROMASTER parameter P2041 (0x27F9*):
The data apply to the mapping set above:
Read FF FF from object 0x27F9 sub 0:
T0 00:00:54,8671: 0x603 8-Data: 40 f9 27 00 00 00 00 00
R0 00:00:54,8856: 0x583 8-Data: 4b f9 27 00 ff ff 00 00
Read 00 FF from object 0x27F9 sub 1:
T0 00:00:54,9398: 0x603 8-Data: 40 f9 27 01 00 00 00 00
R0 00:00:54,9593: 0x583 8-Data: 4b f9 27 01 ff 00 00 00
Read 2103 from object 0x27F9 sub 2:
T0 00:00:55,0574: 0x603 8-Data: 40 f9 27 02 00 00 00 00
R0 00:00:55,0740: 0x583 8-Data: 4b f9 27 02 03 21 00 00
Read 41 41 from object 0x27F9 sub 3:
T0 00:00:55,1647: 0x603 8-Data: 40 f9 27 03 00 00 00 00
R0 00:00:55,1805: 0x583 8-Data: 4b f9 27 03 41 41 00 00