EasyManuals Logo

Siemens MICROMASTER 430 User Manual

Siemens MICROMASTER 430
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
Issue 01/05 Diagnostics and troubleshooting
CANopen Option Module Operating Instructions
6SE6400-5BC00-0BP0
119
7.3 Diagnostic parameters
Parameter r2054
The indexed parameter r2054 provides detailed information if the MICROMASTER
displays a warning (alarm) generated by the CANopen option module.
Index Content
0 Configuration or other errors
0: no error
1: Invalid slave address (low byte of P0918)
2: Invalid PDO Transmission Type (P2041.00 - P2041.01)
3: Invalid T_PDO Transmission Type (P2041.00 - P2041.01)
4: Invalid R_PDO Transmission Type (P2041.01 high byte)
5: Invalid baud rate (P2041.04)
6: Invalid comm error response (P2041.04)
7: Invalid lifeguarding event response (P2041.04)
8 - 10: Unable to read configuration parameters : problem on comm link to Drive
12: Configuration timed out
13: Other configuration error
14 - 15: Configuration Mapping error (P2041.02 – P2041.03)
16: illegal drive type
32: wrong index passed by SDO
33: SDO wrong profile
35 - 36: Failure in writing Parameters to Drive on reset-node
64 - 66: Execution of resetCommunication command failed
67 - 69 Execution of resetNode command failed
96 - 101 Execution of “load” command failed
112 - 113 Execution of “save” failed
114 Tried to do resetcommunication or resetnode whilst drive running
128 - 129 Data set changed, but failed to update parametes accordingly
146 Tried to do resetnode or resetcommunication when data saved to eeprom or
when already executed a “load” command
CANopen errors
401: Out of RAM
402: Object does not exist
404: Operation not allowed in this state
405: No matching type
406: Inhibit time active
407: No initiate service executed
408: Service is already running
409: Datatype does not fit in telegram
410: Errortype does not fit in telegram
412: Invalid range
415: No COB database available
416: Object disabled
420: PDO Mapping error
421: No access to object dictionary
422: Object does not exist
423: Subindex doesn't exist
424: No read permission
425: No write permission
426: Value greater than upper limit
427: Value less than lower limit
428: Object has wrong size
429: Wrong trans type

Table of Contents

Other manuals for Siemens MICROMASTER 430

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MICROMASTER 430 and is the answer not in the manual?

Siemens MICROMASTER 430 Specifications

General IconGeneral
Power Range7.5 kW to 250 kW
Voltage Range380V to 480V
Frequency Range0 Hz to 650 Hz
Protection ClassIP20
Input Frequency47 Hz to 63 Hz
Digital Inputs6
Cooling MethodForced-air cooling
CommunicationUSS
Protection FeaturesOvervoltage, undervoltage, overcurrent, short-circuit, ground fault, overtemperature
Analog Inputs2
Digital Outputs3
Analog Outputs2
Ambient Temperature-10°C to +50°C
Control TypeSensorless vector control

Related product manuals