Diagnostics and troubleshooting Issue 01/05
CANopen Option Module Operating Instructions
120 6SE6400-5BC00-0BP0
430: Hardware fault
431: Parameter incompatible
432: Unknown SDO error
433: SDO command specifier invalid
434: Invalid SDO block size
435: Invalid SDO block crc sum
436: No resources available for SDO connection
437: Bad requested error control mechanism
438: SDO timed out
439: SDO invalid togglebit
440: SDO invalid transmode
441: Bad device state
442: Bad CRC
1 Status of CAN physical layer:
Bits representing CAN errors (because there may be multiple errors)
0: no errors
Bit 0: not used
Bit 1: CAN error passive (CAN error counter(s) >=127, too many error frames)
Bit 2: CAN overflow (too many can messages in a too short time)
Bit 3: error control (Node-guarding or Heartbeat error event)
Bit 4: Sync error (Sync object not received within configured communication cycle)
Bit 5: Bus-Off (CAN controller in Bus-Off state or fatal error on option card)
2 Status of the CANopen network state-machine:
0: CANopen in initialization state
1: Executing a Reset or Fatal Error
2: CANopen in pre-operational state
3: CANopen in stopped state
4: CANopen in operational state
3 counter for PDO telegrams received error-free since power on.
4 counter for telegrams transmitted since power on.
5 counter for all telegrams received error-free since power-on.
this counter includes all CanBus messages, including those not directed to this module.
6 CAN Error counter and Fatal Code
Value > 32767: Fatal Error Code.
0 – 32767 error counter. Counter wraps around back to 1 when count > 32767. Increments
on any CAN passive error, CAN busoff error or CAN overflow error.
If this value is changing rapidly and warning = A0701 then the CAN bus is overloaded.
Reduce Bus loading
If this value is changing rapidly and warning = A0700 or A0702 then the CAN bus is not
healthy.
Check and if required correct most significant digit of P2041.04 (baud rate) for every bus
node
check cable connection between bus nodes
check cable shielding
Reduce Bus loading
replace the CANopen option module