What to do if Siemens Inverter motor fails to start when the ON command has been given?
- Aandrew08Aug 22, 2025
If the Siemens Inverter motor fails to start when the ON command is given, first check that a valid ON signal is present. Also, verify that P0700 = 2 (for digital input control) or P0700 = 1 (for BOP control). Finally, ensure that the setpoint is present (0 to 10V on Terminal 3) or the setpoint has been entered into the correct parameter, depending upon the setpoint source (P1000).