International English                                                                                        3. COMMISSIONING
32 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Changing parameters with the BOP
The following description shows how to change the parameter P1082, use this
description as a guide for setting any parameters using the ‘BOP’.
Step Result on display
1
Press   to access parameters
Hz
P(1)
r0000
2
Press 
  until P0010 is displayed
Hz
P(1)
P0010
3
Press   to access P0010 parameter
value level
Hz
P(1)
0
4
Press 
 to set P0010 = 1
Hz
P(1)
1
5
Press 
  to save and exit parameter
value level
Hz
P(1)
P0010
6
Press 
 until P1082 is displayed
Hz
P(1)
P1082
7
Press 
 to access P1082 parameter
value level
Hz
P(1)
50.00
8
Press   to select desired maximum
frequency
Hz
P(1)
35.00
9
Press 
 to save and exit parameter
value level
Hz
P(1)
P1082
10 Press   to return to P0010
Hz
P(1)
P0010
11
Press   to access P0010 parameter
value level
Hz
P(1)
1
12
Press 
 to return value to P0010 = 0
Hz
P(1)
0
13
Press 
 to save and exit parameter
value level
Hz
P(1)
P0010
14
Press 
  to return to r0000
Hz
P(1)
r0000
15
Press   to exit Parameterization
Hz
P(1)
35.00
The LCD will alternate between actual
frequency and the requested frequency
setpoint
Hz
P(1)
00
.00
Figure 3-4 Changing parameters via the BOP
The required maximum frequency has now been stored.
Note - Busy Message
In some cases - when changing parameter values - the display on the BOP shows
" - - - -". This means the inverter is busy with tasks of higher priority.