EasyManua.ls Logo

Siemens MICROMASTER 430 - Page 19

Siemens MICROMASTER 430
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3 19
Input voltage range 3 AC 500 V – 600 V ± 10 % (Unfiltered)
Order No. 6SE6440- 2UE17
-5CA1
2UE21
-5CA1
2UE22
-2CA1
2UE24
-0CA1
2UE25
-5CA1
2UE27
-5CA1
2UE31
-1CA1
2UE31
-5DA1
Fuse [A]
10 10 10 16 16 25 32 35
Recommended 3N
3803-6 3803-6 3803-6 3805-6 3805-6 3810-6 3812-6 3814-6
for UL specified 3NE
*
*
* * * * * 1803-0
Input Cable Min.
[mm
2
]
1.0 1.0 1.0 1.5 1.5 2.5 4.0 6.0
[awg]
18 18 18 16 16 14 12 10
Input Cable Max.
[mm
2
]
10.0 10.0 10.0 10.0 10.0 10.0 10.0 35.0
[awg]
8 8 8 8 8 8 8 2
Output Cable Min.
[mm
2
]
1.0 1.0 1.0 1.0 1.0 2.5 4.0 4.0
[awg]
18 18 18 18 18 14 12 12
Output Cable Max.
[mm
2
]
10.0 10.0 10.0 10.0 10.0 10.0 10.0 35.0
[awg]
8 8 8 8 8 8 8 2
Order No. 6SE6440- 2UE31
-8DA1
2UE32
-2DA1
2UE33
-0EA1
2UE33
-7EA1
2UE34
-5FA1
2UE35
-5FA1
2UE37
-5FA1
Fuse [A]
50 63 80 80 125 160 160
Recommended 3N
A
3820-6 3822-6 3824-6 3824-6 3132-6 3136-6 3136-6
for UL specified 3NE
1817-0 1818-0 1820-0 1820-0 1022-0 1224-0 1224-0
Input Cable Min.
[mm
2
]
10.0 10.0 16.0 25.0 25.0 50.0 50.0
[awg]
8 8 6 3 3 1/0 1/0
Input Cable Max.
[mm
2
]
35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
2 2 2 2 300 300 300
Output Cable
Min.
[mm
2
]
6.0 10.0 16.0 16.0 25.0 35.0 50.0
[awg]
10 8 6 6 3 2 1/0
Output Cable
Max.
[mm
2
]
35.0 35.0 35.0 35.0 150.0 150.0 150.0
[awg]
2 2 2 2 300 300 300
*UL listed fuses, such as those stated in the warnings on page 2 are required for use in America.
*UL-gelistete Sicherungen, wie in den Warnhinweisen auf Seite 2 angegeben, sind für den Einsatz in Amerika vorgeschrieben.
*Des fusibles homologués UL, tels que ceux mentionnés dans les avertissements à la page 2 sont requis pour une utilisation en Amérique.
*I fusibili omologati UL, come quelli indicati nelle avvertenze a pagina 2, sono richiesti per l'utilizzo sul territorio americano.
*Para uso en Norteamérica se requieren fusibles conformes a UL, como los que figuran en las advertencias de la página 2.

Other manuals for Siemens MICROMASTER 430