P051 Selection control function, DIN1 0 - 19
(terminal 5), fixed frequency 3 [1]
or binary fixed frequency bit 0.
P052 Selection control function, DIN2 0 - 19
(terminal 6), fixed frequency 2. [2]
or binary fixed frequency bit 1.
P053 Selection control function, DIN3 0 - 19
(terminal 7), fixed frequency 1
or binary fixed frequency bit 2. [6]
Value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Function of P051 to P053
Input disabled
ON right
ON left
Reverse
OFF2 **
OFF3 **
Fixed frequencies 1 - 3
Jog right
Jog left
Remote operation
Fault code reset
Increase frequency *
Decrease frequency *
Disable analogue input
(setpoint is 0.0 Hz)
Disable the ability to change
parameters
Enable dc brake
Do not use
Binary fixed frequency control
(fixed frequencies 1 - 7)
As 6, but input high will also
request RUN *
External trip/PTC
Function,
low state
-
Off
Off
Normal
OFF2
OFF3
Off
Off
Off
Local
Off
Off
Off
Analogue on
enabled
Off
-
Off
Off
Yes (F012)
Function,
high state
-
On right
On left
Reverse
On
On
On
Jog right
Jog left
Remote
Reset on
rising edge
Increase
Decrease
Analogue
disabled
disabled
Brake on
-
On
On
No
* Only effective when P007 = 0.
** See section 4.3.
Binary Coded Fixed Frequency Mapping
(P051, P052, P053 = 17)
DIN3
(P053)
DIN2
(P052)
DIN1
(P051)
STOP 0 0 0
RUN to FF1 (P041) 0 0 1
RUN to FF2 (P042) 0 1 0
RUN to FF3 (P043) 0 1 1
RUN to FF4 (P044) 1 0 0
RUN to FF5 (P046) 1 0 1
RUN to FF6 (P047) 1 1 0
RUN to FF7 (P048) 1 1 1
P056
Digital input debounce time 0 - 2
[0]
0 = 12.5 ms
1 = 7.5 ms
2 = 2.5 ms