Flow Application Configuration
Configuring the MultiRanger 200 to measure open channel flow
Specific parameter setting to configure the following primary measurement devices:
Objective:
exponential devices
Palmer-Bowlus Flume
H-Flume
Universal Linear Flow Calculation
Universal Curved Flow Calculation
BS 3680/ISO 4359 Rectangular Flume
BS 3680/ISO 1438/1 Thin Plate V-Notch Weir
Equipment:
MultiRanger 200, transducer, IR Hand Held Programmer or Dolphin Plus software, and primary
measurement device.
While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied.
Overview:
This application guide is an addition to the instruction manual. Please review manual to ensure you are familiar with configuring
the MultiRanger 200 using the IR Hand Held Programmer or the Dolphin Plus software tool.
Setting up the Common Parameters
These parameters are configured for all the open channel flow measuring applications supported by the MultiRanger 200.
Parameter Parameter Index* Value Parameter and Value Definition **
P001 G 6 Selects Open Channel Flow measurement.
P002 G 1 Sets measured material to liquid.
P003 G 2 Sets maximum processing speed, or speed of response, to
medium.
P004 G 102 (example) Selects transducer (e.g. 102 = XPS 10) connected to MultiRanger
200.
P005 G 1 (example) Sets units for head measurement (e.g 1 = meters).
P006 G Empty Distance Sets the distance from zero point of measurement (many times
bottom of the weir or channel) to the sensor surface. Head is
measured with reference to this zero point
P007 G Span of Head
measurement
Sets the range of head measurement. Often equal to the maximum
head.
P801 G Range Extension Permits the liquid level to go below the zero point to the amount set
here without indicating an LOE condition (pre-set is 20% of span).
* G means ‘global.’ If f you have dual channel unit then the index is either 1 or 2 . For both, select 00.
** Here we have chosen one value. Other choices can be selected from the manual as needed.
APPLICATION GUIDE

Other manuals for Siemens multiranger 200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens multiranger 200 and is the answer not in the manual?

Siemens multiranger 200 Specifications

General IconGeneral
TypeUltrasonic level transmitter
Frequency50 kHz
Output4 to 20 mA
Communication ProtocolProfibus DP
Enclosure RatingIP67
DisplayLCD
Process Connection2" NPT
Process Temperature-40°C
Process PressureUp to 3 bar
Operating Temperature-20 to +60 °C (-4 to +140 °F)

Related product manuals