EasyManua.ls Logo

Siemens MXL - Page 2

Siemens MXL
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Document No. 565-957
Installation Instructions
August 12, 2005
1. Follow all shutdown procedures necessary to
prevent damage to any equipment or harm to any
personnel.
2. Turn OFF power to the MEC/MBC/RBC en closure.
3. In the MXL enclosure, locate the NIM-1R or
NIM-1W module (hereafter referred to as the
NIM-1 module). This module will be plugged into
the connectors on a MOM-2 or MOM-4 module. If
it is plugged into a MOM-4 module, note w hether
the NIM-1 module is plu gged into the slot closest
to the terminal block labeled TB3 or TB4.
4. If the NIM-1 is plugged into a MOM-2 module,
or if it is plu gged into the slot closest to te rminal
block TB4, the follo win g instruc tions apply to
connections on TB4. If the N IM-1 module is
plugged into a MOM-4 module, in the slot closest
to TB 3, the instructions apply to connec tions on
TB3.
5. Connect one end of the shielded twisted pair
cable to terminal 1 and 2 on the appropriate
terminal block, as specied above. Terminal 1
is the negative (-) terminal, and terminal 2 is
the positive (+) terminal. There is no terminal
available for the shield, so it will be connected at
the driver. (See Figure 1 and Figure 2.)
6. Connect a 120-ohm, 1/4 watt resistor between
terminals 3 and 4 of this same terminal block.
See Figure 2 .
7. At the MEC /MBC/RBC, attach the +, -, and S
leads of the RS-485 cable to an FLN/PMD trunk
connector. Allow an additional 12 inches (305
mm) of cable before terminating to the connector.
The standard practice used by MXL
installers would also require a 120-ohm
resistor between terminals 1 and 2.
Do NOT install a resistor across these
terminals.
8. Turn ON power to the MEC/MBC/RBC enclosure.
9. Start any other equipment that might have been
shut d own fo r this installation.
FLN
DRIVER
S
-
+
MXL PANEL
TAPE BACK
SHIELD
GW1326R1
RS-485 TRUNK CABLE
(MAX 4000’/1219.2 m;
STANDARD 24 AWG LOW CAPACITANCE)
1
2
3
4
TB3
or
TB4
NIM-1 MODULE
120 ohms
1/4 watt
resistor
Figure 1. Connecting the Siemens MXL Driver to the MXL System.
Page 2 of 4
Siemens Building Technologies, Inc.

Related product manuals