4BMounting / Installation
28BDetector base seal RS720
5
39 |
64
Building Technologies
A6V10212047_m_en_--
Fire Safety
2015-05-04
5.4 Detector base seal RS720
Use the detector base seal RS720 to install point detectors in wet rooms.
Protection category: IP42.
Compatible with the detector bases DB72x and the sounder base DBS720.
Only use for recess-mounted cable entry.
Installing the detector base seal
1. NOTICE! Excessively large holes in the detector base seal will impair the
potential IP protection category. Do not cut or drill holes in the detector base
seal. Without using a tool, push the lines through the detector base seal.
2. Fit the detector base seal RS720 between the ceiling and the detector base
DB72x or the sounder base DB720.
Figure 4: Installing the detector base seal RS720
See also
Detector base seal RS720 [➙ 27]