EasyManua.ls Logo

Siemens OH720 - Technical Specifications; Multi-Sensor Smoke Detector Technical Data

Siemens OH720
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7BSpecifications
40BMulti-sensor smoke detector technical data
8
54
| 64
A6V10212047_m_en_--
2015-05-04
8 Specifications
Unless otherwise mentioned, the following data applies:
Temperature = 25 °C
Air pressure = 1000 hPa (750 Torr)
8.1 Multi-sensor smoke detector technical data
The following section lists the technical data for the multisensor smoke detector
OH720.
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document A6V10202198
Detector line
Operating voltage (modulated) DC 12…33 V
Operating current (quiescent) Typ. 230 μA
Maximum current connection factor 1
Quiescent current connection factor 1
Address connection factor 1
Separator connector factor 1
Protocol C-NET
Compatibility See 'List of compatibility'
Line separator
Line voltage:
Nominal DC 32 V (= V
nom
)
Minimum DC 12 V (= V
min
)
Maximum DC 33 V (= V
max
)
Voltage at which the line separator opens:
Minimum DC 7.5 V (= V
SO min
)
Maximum DC 10.5 V (= V
SO max
)
Permanent current when switches are closed: Max. 1.5 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 2 A (= I
S max
)
Leakage current when switches are open: Max. 1 mA (= I
L max
)
Serial impedance when switches are closed: Max. 0.4 Ω (= Z
C max
)
The line separator is closed via an actuation signal from the control panel. Required line
voltage: DC 12...33 V (normal range)
External alarm indicators
Number of external alarm indicators that can
be connected
Max. 2
Voltage DC 9…30 V
Current 10…16 mA

Table of Contents