B-8
Manual OP5, OP15
( ) J31069-D0840-U001-A2-7618
ActionCauseMessage
$ 533 No connection between OP and
floppy disk station
Connection cable not plugged in
or is defective
Error on the floppy disk station
Floppy disk station not ready
$ 534 No more memory space on the
floppy disk
Insert a blank, formatted floppy disk and trig-
ger transfer again.
$ 535 No floppy disk inserted
Floppy disk defective
Floppy disk not formatted
Insert new, formatted floppy disk
$ 536 Malfunction in the connection be-
tween OP and floppy disk station
Connection cable defective or
not plugged in correctly
$ 537 Read access to blank floppy disk
$ 538 Simultaneous access to data record
via job and operator input
Repeat access which was not executed
$ 540 Maximum number of data records
already set up
$ 600 Wrong parameter transferred by
ProTool/Lite
(overflow warning)
Set required value by means of standard
screen or PLC
$ 601 Wrong parameter transferred by
ProTool/Lite
(message log)
Set required value by means of standard
screen or PLC
$ 602 Wrong parameter transferred by
ProTool/Lite
(remaining buffer size)
Re-configure and repeat download of required
value
$ 604 Message not configured for a set
message bit
Configure messages and transfer
$ 613 Data block does not exist or is too
short
Create DB of requisite length in PLC
$ 615 Line to be output is larger than the
reserved print memory or the num-
ber of control sequences is too large
Check configuration for log
$ 616
$ 617
See Internal Errors
System Messages