C-3
Manual OP5, OP15
( ) J31069-D0840-U001-A2-7618
OP5 OP15
A1 A2 A1 A2 A1-VF A2-VF C1 C2
Ambient Conditions
Ambient temperature,
operation
Vertical installation
Horizontal installation
Transportation, storage
0° Cto45°C
0°C to 35° C
–25° C to 70° C
0° Cto55°C
0°C to 45° C
–25° C to 70° C
0° Cto45°C
0°C to 35° C
–25° C to 70° C
Relative humidity
Operation
Transportation, storage
95%, no condensation
95%
Shock load
Operation
Transportation, storage
5 g/11 msec
25 g/6 msec
Vibration
Operation
Transportation, storage
0.075 mm/1 g
3.5 mm/1 g
Max. pressure differ-
ence (front, back)
2 hPa
Air pressure
Operation
Transportation, storage
706 to 1030 hPa
581 to 1030 hPa
Interference Immunity (EN 50082-1)
Static discharge
(contact discharge)
IEC 801-2 class 3
RF irradiation ENV 50140 class 3
Burst interference IEC 801-4 class 3
Pulse modulation ENV 50204
Interference Emission (EN 50081-1)
RFI suppression level In accordance with VDE 0878, EN 55022