Accessories
7.1 Reactor and filter
PM250 Power Module
64 Hardware Installation Manual, 09/2012, A5E01003502B AD
Technical specifications of the sine-wave filter
The major electrical specification of the sine-wave filter is the same as for the suitable Power
Module. This applies to:
● voltage
● current
The maximum permissible output frequency of the Power Module is 150 Hz when a sine-
wave filter is used – the pulse frequency must not exceed 8 kHz.
The admissible ambient conditions of the sine-wave filter are the same as for the suitable
Power Module. This applies to:
● storage and transport temperature
● operating temperature
● relative humidity
● shock and vibration load
Table 7- 5 Technical specifications of the sine-wave filters (table 1 of 3)
Suitable for Power Module with rated power (HO) of
5.5 kW 7.5 kW … 11 kW
Feature
FSC FSC
MLFB of the sine-wave
filter
6SL3202-0AE22-0SA0 6SL3202-0AE23-3SA0
MLFB of the suitable Power
Module
6SL3225-0BE25-5 . A0 6SL3225-0BE27-5 . A0
6SL3225-0BE31-1 . A0
dv/dt limiting ≤ 500 V/µs ≤ 500 V/µs
Power loss at 50 Hz 40 W 65 W
Motor connection Screw terminals 10 mm² Screw terminals 10 mm²
Connection to Power
Module
Cable, 500 mm length Cable, 500 mm length
Degree of protection IP20 IP20
Overall dimensions
Width
Height
Depth
189 mm
336 mm
140 mm
189 mm
336 mm
140 mm
Installation clearance
Top
Bottom
Side
100 mm
100 mm
100 mm
100 mm
100 mm
100 mm
Fixing dimensions
Width
Height
167 mm
323 mm
167 mm
323 mm
Fixing screw 4 × M5 4 × M5
Weight 12.0 kg 23.0 kg
Possible as base
component
yes yes