48/221
Siemens Switzerland Ltd User manual RVS61.843 CE1U2355en_02
HVAC Products 5 Handling 23. November 2007
Operating
line
operating
Function
Default value
Minimum
Max
Unit
963 F
With prim contr/system pump
No ¦ Yes
No -
969 F Optg mode changeover
None ¦ Off ¦ Automatic
Off
-
Heating circuit 2
1010 E
Comfort setpoint
20.0 Op line 1012 Operating line 1016 °C
1012 E Reduced setpoint 16 Op line 1014 Operating line 1010 °C
1014 E
Frost protection setpoint
10.0 4 Operating line 1012 °C
1016 F Comfort setpoint max 35.0 Op line 1010 35 °C
1020 E Heating curve slope 1.50 0.10 4.00 -
1021 F Heating curve displacement 0.0 -4.5 4.5 °C
1026 F Heating curve adaption
Off ¦ On
Off
-
1030 E Summer/winter heating limit 18 − − − / 8 30 °C
1032 F 24-hour heating limit -3 − − − / -10 10 °C
1040 I
Flow temp setpoint min
8 8 Operating line 1041 °C
1041 I
Flow temp setpoint max
80 Op line 1040 95 °C
1050 F Room influence 20 − − − / 1 100 %
1060 F Room temp limitation 1 − − − / 0.5 4 °C
1070 F Boost heating 5 − − − / 0 20 °C
1080 F Quick setback
Off ¦ Down to reduced setpoint¦Down to frost prot setpoint
Down to reduced setpoint -
1090 F Optimum start control max 0:00:00 00:00:00 00:06:00
h /min / s
1091 F Optimum stop control max 0:00:00 00:00:00 00:06:00
h /min / s
1100 F Reduced setp increase start − − − − − − / -30 10 °C
1101 F Reduced setp increase end -15 -30 Operating line 1100 °C
1120 F Overtemp prot pump circuit
Off ¦ On
On
-
1130 F Mixing valve boost 5 0 50 °C
1132 F
Actuator type
2-position ¦ 3-position
3-position -
1133 F Switching differential 2-pos 2 0 20 °C
1134 F Actuator running time 120 30 873 s
1150 I Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/
curing heating¦ Curing/functional heating ¦ Manually
Off. -
1151 E
Floor curing setp manually
25 0 95 °C
1155 E Floor curing setp current − − − 0 95 °C
1156 E Floor curing day current − − − 0 32 °C
1157 I
Floor curing days completed
0 0 32 -
1161 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always
1170 F
With buffer
No ¦ Yes
Yes -
1172 F
With prim contr/system pump
No ¦ Yes
Yes
1200 I Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection
Heating circuit P
1300 E Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatically -
1310 E
Comfort setpoint
20.0 Op line 1312 Operating line 1316 °C