Siemens Switzerland Ltd User manual RVS61.843 CE1U2355en_02
HVAC Products 5 Handling 23. November 2007
Operating
line
operating
level
Function
Default value
Minimum
Max
Unit
1312 E Reduced setpoint 19 Op line 1314 Operating line 1310 °C
1314 E
Frost protection setpoint
10.0 4 Operating line 1312 °C
1316 F Comfort setpoint max 35.0 Op line 1310 35 °C
1320 E Heating curve slope 0.8 0.10 4.00 -
1321 F Heating curve displacement 0.0 -4.5 4.5 °C
1326 F Heating curve adaptation
Off ¦ On
Off. -
1330 E Summer/winter heating limit 18 / 8 30 °C
1332 F 24-hour heating limit -3 / -10 10 °C
1340 I
Flow temp setpoint min
8 8 Operating line 1341 °C
1341 I
Flow temp setpoint max
50 Op line 1340 95 °C
1350 F Room influence 20 / 1 100 %
1360 F Room temp limitation 1 / 0.5 4 °C
1370 F Boost heating / 0 20 °C
1380 F Quick setback
Off ¦ Down to reduced setpoint¦Down to frost prot setpoint
Down to reduced setpoint -
1390 F Optimum start control max 0:00:00 00:00:00 00:06:00
h /min / s
1391 F Optimum stop control max 0:00:00 00:00:00 00:06:00
h /min / s
1400 F Reduced setp increase start / -30 10 °C
1401 F Reduced setp increase end -15 -30 Operating line 1400 °C
1420 F Overtemp prot pump circuit
Off ¦ On
Off. -
1450 F Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off. -
1451 F
Floor curing setp manually
25 0 95 °C
1455 E Floor curing setp current 0 0 95 °C
1456 E Floor curing day current 0 0 32 -
1457 I
Floor curing days completed
0 0 32 -
1461 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always -
1470 F
With buffer
No ¦ Yes
Yes -
1472 F
With primary contr / system pump
No ¦ Yes
Yes -
1500 I Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection -
Domestic hot water
1610 E Nominal setpoint 50 Op line 1612 TempBwMax °C
1612 E Reduced setpoint 40 8 Operating line 1610 °C
1620 I
Release
24h/day ¦ Time programs HCs ¦ Time program 4 / DHW
Time program 4 / DHW -
1630 I Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
Absolute -
1640 F
Legionella function
Off ¦ Periodically ¦ Fixed weekday
Off
-
1641 F Legionella funct periodically 3 1 7 Days
1642 F Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦
Saturday ¦ Sunday
-
1644 F
Legionella func time
/ 00:00 23:50 hh:mm
1645 F
Legionella func setpoint
65 55 95 °C