50/221
Siemens Switzerland Ltd User manual RVS61.843 CE1U2355en_02
HVAC Products 5 Handling 23. November 2007
Operating
line
operating
Function
Default value
Minimum
Max
Unit
1646 F Legionella funct duration − − − − − − / 10 360 min
1647 F Legionella funct circ pump
Off ¦ On
On. -
1660 F Circulating pump release
Time program 3 / HCP ¦ DHW release ¦ Time program 4 /
DHW ¦ Time program 5
Time program 3 / HCP -
1661 F Circulating pump cycling
Off ¦ On
On
-
1663 F Circulation setpoint 45 8 80 °C
Pump Hx
2010 F H1 Excess heat draw
Off ¦ On*
On
-
2012 F
H1 with buffer
No ¦ Yes*
Yes -
2014 F H1 prim contr/system pump
No ¦ Yes*
Yes -
2015 F
H1 Refrigeration request
2-pipe system* ¦ 4-pipe system
2-pipe system -
2035 F H2 Excess heat draw
Off ¦ On*
On. -
2037 F
H2 with buffer
No ¦ Yes*
Yes -
2039 F H2 prim contr/system pump
No ¦ Yes*
Yes -
2040 F
H2 Refrigeration request
2-pipe system* ¦ 4-pipe system
2-pipe system -
2046 F H3 Excess heat draw
Off ¦ On*
On
-
2048 F H3 with buffer
No ¦ Yes*
Yes -
2050 F H2 prim contr/system pump
No ¦ Yes*
Yes -
2051 F
H3 Refrigeration request
2-pipe system ¦ 4-pipe-system
2-pipe system -
Swimming pool
2055 E Setpoint solar heating 26 8 80 °C
2056 E
Setpoint source heating
22 8 80 °C
2065 F Charging priority solar
No ¦ Yes
No -
2080 F With solar integration
No ¦ Yes
Yes -
Primary controller / system pump
2150 I
Prim contr/system pump
Before buffer st tank ¦ After buffer st tank
After buffer st tank -
Heat pump
2800 F Frost protection cond pump
Off ¦ On
Off. -
2801 I
Control cond pump
Automatically ¦ Temp request ¦ Parallel compr operation
Parallel compr operation
-
2802 I Prerun time cond pump 5 0 240 s
2803 I Overrun time cond pump 5 0 240 s
2815 F
Source temp min water
2 − − − / -20 30 °C
2816 F
Source temp min brine
-5 − − − / -30 50 °C
2817 F Switching diff source prot 3 1 10 °C