Building Technologies 2014-09-26
Operating page "RF"
No. Operating line Settings
120** Binding No ¦ Yes
121** Test mode Off ¦ On
* QAA78 only
For more detailed information, refer to the descriptions in Section "Wireless
components" [➙ 17].
When commissioning the system, the wireless peripheral devices (room units) are
assigned to the basic unit.
The test mode is used for checking the radio link. The test should be made when
the installation is entirely completed.
No. Operating line Settings
130 Room unit 1 Missing ¦ In operation ¦ No recept'n ¦ Change batt
131 Room unit 2 Missing ¦ In operation ¦ No recept'n ¦ Change batt
132 Room unit 3 Missing ¦ In operation ¦ No recept'n ¦ Change batt
133 Outside sensor Missing ¦ In operation ¦ No recept'n ¦ Change batt
134 RF repeaters Missing ¦ In operation ¦ No recept'n ¦ Change batt
135 Operator unit 1 Missing ¦ In operation ¦ No recept'n ¦ Change batt
136 Operator unit 2 Missing ¦ In operation ¦ No recept'n ¦ Change batt
137 Operator unit 3 Missing ¦ In operation ¦ No recept'n ¦ Change batt
138 Service unit Missing ¦ In operation ¦ No recept'n ¦ Change batt
140 Delete all devices No ¦ Yes
The radio link to all devices will be cancelled. If radio communication is required
again, a new binding must be established.
Binding
Binding
Test mode
RF device list
Delete all devices