Installation SDQLCAI-1
2-2 May 2002
2.1.2 Marshalled Termination Assembly Identification
The CAI can be used with the CAI/SAI Marshalled Termination Assembly. This assembly is identified
by the following information printed on its surface.
CAI/SAI
MARSHALLED
TERMINATION
P/N 16428-1
2.2 Preparations
1. Install the MODULRAC (SIXRAC, or Remote I/O Rack) in the cabinet where the CAI is to be
installed. The CAI should not be installed in the rack at this time; however, its designated slot
number should be known.
2. If remote I/O termination is employed, complete the following tasks:
If Marshalling Utility Panels are being used, install them in their respective marshalling cabinets.
Tag all I/O cables and route them into the marshalling cabinet. They should be ready for cable
end preparation and connection to the CAI/SAI Marshalled Termination Assemblies. Cable wire
sizes: 24 to 12 AWG.
Route the Interconnect I/O Cable (or Unterminated I/O Cable) between the rack in which the CAI
is to be installed and the marshalling cabinet. Refer to Figure 1-1; the J1 end of the cable is to be
installed in the rack and P2 end is to be connected to the appropriate Marshalled Termination
Assembly in the marshalling cabinet.
If an Unterminated I/O Cable is installed, you must supply and install the appropriate termination
hardware (terminal blocks) for field signal I/O wiring and the I/O Cable.
3. If channel diagnostics are to be used for automatically detecting wiring faults such as short or open
circuits, each channel must be wired with the appropriate resistors (and configured accordingly).
High-power EMI-producing equipment should not be connected to any power lines dedicated to CAI
input signals.
2.3 Environmental Considerations
Many industrial environments create severe operating conditions. The conditions at each CAI
location must be within the specifications stated in section 6.2.
To ensure operator safety, Marshalled Termination Assemblies shall be installed in enclosures, which
require a key or special tool to gain access to the equipment.