RDF301, RDF301.50..., RDF600KN
The thermostat's operating mode can be influenced in different
The following operating modes are available:
In Auto Timer mode the room operating mode is commanded via bus.
Auto Timer is replaced by Comfort when no time schedule via bus is present
In Comfort mode, the thermostat maintains the Comfort setpoint. This setpoint can
It can be locally adjusted via the
In Comfort mode, the fan can be set to automatic or manual fan speed: Low,
The thermostat switches to
previous operating mode set by the hotel guests.
The setpoints (less heating and cooling than in Comfort mode) can be defined via
The thermostat switches to
the operating mode button is pressed (only possible if parameter P02 is set to 2)
an operating mode switchover contact
presence detector (P02 is irrelevant) *)
In Protection mode, the system is...
protected against frost (factory setting 8 °C, can be disabled or changed via
protected against overheating (factory setting OFF, can be enabled or changed
The thermostat switches to Protection mode when...
the operating mode button is pressed
Room operating mode:
State
Auto Timer
Comfort
Presence detector
(RDF600KN…)
Economy
Room operating mode:
Window state
(RDF301…)
Protection
Room operating mode:
Window state
(RDF600KN…)
Note:
RDF301, RDF301.50..., RDF600KN
The thermostat's operating mode can be influenced in different
heating and cooling setpoints
room operating mode on the bus.
The following operating modes are available:
In Auto Timer mode the room operating mode is commanded via bus.
Auto Timer is replaced by Comfort when no time schedule via bus is present
In Comfort mode, the thermostat maintains the Comfort setpoint. This setpoint can
It can be locally adjusted via the
In Comfort mode, the fan can be set to automatic or manual fan speed: Low,
The thermostat switches to
, the thermostat switches to Economy mode
local HMI (keys) is locked. Upon
occupancy, the thermostat
previous operating mode set by the hotel guests.
The setpoints (less heating and cooling than in Comfort mode) can be defined via
The thermostat switches to
the operating mode button is pressed (only possible if parameter P02 is set to 2)
an operating mode switchover contact
tor, window contact) is active. *)
via bus, e.g. from a KNX switch or a KNX
presence detector (P02 is irrelevant) *)
In Protection mode, the system is...
protected against frost (factory setting 8 °C, can be disabled or changed via
protected against overheating (factory setting OFF, can be enabled or changed
ting mode can be selected locally if Protection mode is commanded
The thermostat switches to Protection mode when...
the operating mode button is pressed
via bus, e.g. from a KNX switch *)
for detail regarding the operating mode switchover
...), window contact (RDF600KN…
The thermostat's operating mode can be influenced in different
room operating mode on the bus.
In Auto Timer mode the room operating mode is commanded via bus.
Auto Timer is replaced by Comfort when no time schedule via bus is present
In Comfort mode, the thermostat maintains the Comfort setpoint. This setpoint can
In Comfort mode, the fan can be set to automatic or manual fan speed: Low,
, the thermostat switches to Economy mode
occupancy, the thermostat
The setpoints (less heating and cooling than in Comfort mode) can be defined via
the operating mode button is pressed (only possible if parameter P02 is set to 2)
via bus, e.g. from a KNX switch or a KNX
protected against frost (factory setting 8 °C, can be disabled or changed via
protected against overheating (factory setting OFF, can be enabled or changed
ting mode can be selected locally if Protection mode is commanded
via bus, e.g. from a KNX switch *)
for detail regarding the operating mode switchover