P60 = OFF
P15 is not implemented into RDF600KN SW
When the fan starts from standstill, it starts at speed 3 for 1 second to
fan motor start by overcoming inertia and friction (selected via parameter P58).
Q
Q3
Q2
Q1
0
1 sec
When the
(parameter P54) to avoid overtemperature of the
thermal cutout from responding.
In case of fan failure, the
overtemperature.
safety device (thermal cutout).
The "C
lean fan filter reminder
message
"
threshold is reached. This does not impact
continues to run normally.
The "C
lean filter reminder
Protection
In Auto Timer mode
changed to
default mode after each switchover from Comfort to
versa.
To let the heating / cooling coil reach its temperature, the fan start can be delayed
by a time period set via parameter P67.
Y
0
P 67
1
Q
This function (via parameter P67) is not implemented into RDF600KN SW
< V1.8.
Note:
Fan start
Fan overrun for electric
heater
Fan failure
Clean fan filter
reminder
Fault information
Fan in Auto Timer
mode
Fan start delay
(RDF600KN…)
Note:
RDF301, RDF301.50..., RDF600KN
, RDF600KN/S Basic D
P60 = OFF
Fan operation in dead zone according to P15
P15 is not implemented into RDF600KN SW
version < V1.
When the fan starts from standstill, it starts at speed 3 for 1 second to
fan motor start by overcoming inertia and friction (selected via parameter P58).
T
1 sec
3181D22
When the
electric
heater is switched off, the fan overruns for 60 seconds
(parameter P54) to avoid overtemperature of the
electric
heater or prevent
thermal cutout from responding.
In case of fan failure, the
thermostat cannot protect the
electric
overtemperature.
For this reason, the electric
heater must feature a separate
safety device (thermal cutout).
lean fan filter reminder
"
function counts the fan operating hours and displays
"
FIL "
to remind the user to clean the fan filter as soon as the
threshold is reached. This does not impact
the
thermostat's
continues to run normally.
The function is set via
parameter P62 (default = OFF
lean filter reminder
" is reset when the
operating mode is manually set to
and back.
In Auto Timer mode
, the
default fan mode is automatic. The fan mode can be
changed to
Manual by pressing
the FAN button. The fan returns to the automatic
default mode after each switchover from Comfort to
Economy
To let the heating / cooling coil reach its temperature, the fan start can be delayed
by a time period set via parameter P67.
T
P 67
31 81 D23
T
This function (via parameter P67) is not implemented into RDF600KN SW
ocumentation
CE1P3171en
2017-12-07
Fan operation in dead zone according to P15
.
version < V1.
8.
When the fan starts from standstill, it starts at speed 3 for 1 second to
ensure safe
fan motor start by overcoming inertia and friction (selected via parameter P58).
heater is switched off, the fan overruns for 60 seconds
heater or prevent
the
electric
heater against
heater must feature a separate
function counts the fan operating hours and displays
to remind the user to clean the fan filter as soon as the
thermostat's
operation, which
parameter P62 (default = OFF
(0)).
operating mode is manually set to
default fan mode is automatic. The fan mode can be
the FAN button. The fan returns to the automatic
Economy
mode, and vice
To let the heating / cooling coil reach its temperature, the fan start can be delayed
This function (via parameter P67) is not implemented into RDF600KN SW
version

Table of Contents

Other manuals for Siemens RDF301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF301 and is the answer not in the manual?

Siemens RDF301 Specifications

General IconGeneral
BrandSiemens
ModelRDF301
CategoryThermostat
LanguageEnglish

Related product manuals