● In Edit mode (value flashes), press to delete schedule or (Esc) to cancel
the change. The maximum number of set schedules is three per day.
● In same schedule, the switching point for Economy cannot be earlier than that
for Comfort. E.g. Comfort is from 8:00 to 11:00 and Economy from 11:00 to
15:00. The edited switching point for Economy starts at 10:30. Afterwards,
press once to confirm the change. No other schedule can be viewed until
the Economy switching point is set later than 11:00.
If the start time or end time of a new schedule lies within range of an existing
schedule, the schedule is combined with the existing one (OR function).
Example 1:
The 1
st
schedule is 8:00…12:00 and the 2
nd
is 13:00…17:00. If the newly added
schedule starts at 10:00 and ends at 12:30, the schedule order is 1
st
schedule
(8:00…12:30) and 2
nd
schedule (13:00…17:00) after the change is confirmed by
pressing .
Example 2:
The 1
st
schedule is 8:00…12:00 and the 2
nd
is 13:00…17:00. If the newly added
schedule starts at 10:00 and ends at 13:30, the schedule is 8:00…17:00 after
the change is confirmed by pressing .
For apartments with local scheduler and time / date synchronization via KNX
When the local scheduler is enabled (P005):
• When P002 (operation via room op. selector) = 1 or 2, the manual selected
operating mode on the HMI remains in that mode until the user intervention to
select a new operating mode. P002 = 3 is no longer available.
• When Auto is selected, the thermostat works according to the local scheduler
(operating mode switches between Comfort or Economy).
• In Auto Comfort, changing the setpoint value does not switch the operating
mode to Comfort permanently.
• In Auto Economy, changing the setpoint value switches the operating mode to
Auto Comfort with the new setpoint. Temporary timer symbol is displayed.
Selecting green/red leaf function resets operating mode back to Auto Economy.
The local scheduler takes priority over the bus scheduler. KNX room "op.mode: