Functions
Control sequences
4
A6V11545892_en--_c
87 | 180
Heating and cooling mode (P001 = 4)
Heating mode with manual selection
(P001 = 3) or
to save energy (P010 = 2 & P014) in the
heating sequence
Cooling mode with manual selection
(P001 = 3) or
to save energy (P010 = 2 & P015) in the
cooling sequence
T[°C] Room temperature
YH1, YC1 Control command "Valve"
stage 1
w Room temperature setpoint
YH2, YC2 Control command "Valve"
stage 2
X
dz
Dead zone (P055)
XpH Proportional band "Heating"
(P050)
w
D
Setpoint differential (P056)
XpC Proportional band "Cooling"
(P052)
Modulating control:
PWM or DC 0…10 V
Note
Note