Siemens Room temperature controllers CE1N3070en
Building Technologies 20.11.2007
conformity to
EMC directive 2004/108/EC
Low-voltage directive 2006/95/EC
Radio equipment 1999/5/EC
N 474
C-tick conformity to
Test standards and requirements EN 61000-6-3, AS/NZS 4251.1: 1999
Test standards for radio equipment AS/NZS 4268: 2003
Product safety
Automatic electrical controls for EN 60 730-1 and
household and similar use EN 60 730-2-9
Information technology equipment -
Safety - General Requirements EN 60950-1
Generic standards - Compliance to
lower power electronic apparatus EN 50371-1
Electromagnetic compatibility and radio
spectrum matters–Short range devices EN 300220-3 V1.1.1
Electromagnetic compatibility and radio
spectrum matters – EMC EN 301489-3 V1.4.1
Safety class III as per EN 60950-1
Pollution degree 2
Degree of protection of housing IP20
Weight (incl. package)
RDH10RF/SET 515 g
Color of housing front Signal-white RAL 9003
Housing material ABS (LCD lens: PC)
Receiver RCR10/433
Operating voltage
Power
AC 230 V +10/15%
<10 VA
Frequency 50...60 Hz
Switching capacity of relays
Voltage
Current
AC 24...250 V
8 (3) A
Relay contacts
Switching voltage Max. AC 250 V
Min. AC 24 V
Switching current Max. 8 A res., 3 A ind.
At 250 V Min. 200 mA
Contact life at AC 250 V Guide value:
At 5 A res. 1 x 10
5
cycles
Insulating strength
Between relay contacts and coil AC 5,000 V
Between relay contacts (same pole) AC 2,500 V
Connection terminals Screw terminals
For solid wires 2 x 1.5 mm
2
For stranded wires 1 x 2.5 mm
2
(min. 0.5 mm
2
)
Standards
General
General unit data
Outputs
Switching outputs
(LX, L1, L2)
Electrical connections

Other manuals for Siemens RDH10RF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDH10RF and is the answer not in the manual?

Siemens RDH10RF Specifications

General IconGeneral
MountingWall-mounted
WirelessYes
DisplayLCD
Frost ProtectionYes
Power SupplyBattery
Set Temperature Range5°C to 30°C