143/218
Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of heating engineer settings 26.03.2001
4.78.4 Heat demand DC 0...10 V
External consumers can transmit a demand for heat in the form of an analog signal of
DC 0...10 V. The controller converts this voltage signal to a temperature setpoint of
0...130 °C and considers this value when generating the setpoint of boiler temperature
control.
[v]
0
2
4
6
8
10
S = 5°C
T = maximum value of heat demand
S = minimum limitation of heat demand = 5 °C
The setpoint for 10 V can be set with parameter “Maximum value of heat demand”
(operating line 172, setting range 5...130 °C). The voltage corresponding to the
displayed temperature can then be calculated as follows:
C][ demand" heat of value Maximum"