Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Handling 26.03.2001
2 Handling
2.1 Installation
2.1.1 Regulations for installation
Air circulation around the controller must be ensured, allowing the unit to emit the
heat produced by it.
A clearance of at least 10 mm must be provided for the controller's cooling slots
which are situated a the top and bottom of the housing.
The space should not be accessible and no objects should be placed there.
If the controller is enclosed in another closed (insulating) casing, a clearance up to
100 mm must be observed on all sides
The controller is designed conforming to the directives for safety class II mounted in
compliance with these regulations
Power to the controller may be supplied only after it is completely fitted in the cut-out.
If this is not observed, there is a risk of electric shock hazard near the terminals and
through the cooling slots
The controller may not be exposed to dripping water
Permissible ambient temperature when mounted and when ready to
operate: 0...50 °C
2.1.2 Mounting location
In the boiler front
In the control panel front
2.1.3 Mounting procedure
Turn off power supply
Pull the prefabricated cables through
the cut-out
Plug the connectors into the
respective sockets at the rear of the
controller
è Note:
The connectors are coded to make
certain they cannot be mixed up.
2373Z05
1. Making the
connections