Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Summary 26.03.2001
1 Summary
1.1 Brief description
The ALBATROS controllers described in this documentation are designed for
integration in mass-produced heat generating equipment and offer the following control
choices:
Single- or 2-stage burner, modulating burner, one BMU
D.h.w. charging pump or diverting valve
3-position mixing valve and circulating pump
Various applications via multi-functional outputs
The range of products comprises several units that are complementary in terms of
application and scope of functions. The controllers have communication capability and
can be combined to form extensive heating systems.
For more detailed information about the generation of LPB systems, refer to “Local
Process Bus (LPB), Basic Documentation, System Engineering“, document no.
CE1P2370E.
1.2 Features
Heating controller for mixing and / or pump heating circuits with:
weather-compensated flow temperature control
weather-compensated flow temperature control with room influence
2 separately controlled heating circuits (one mixing and / or one pump heating circuit
or 2 pump heating circuits)
Quick setback and boost heating
Automatic 24-hour heating limit
Automatic summer / winter changeover
Remote operation via digital room unit
The building's thermal dynamics are taken into consideration
Automatic adjustment of the heating curve to the type of building construction and
the heat demand (provided a room unit is connected)
Adjustable flow temperature boost with mixing heating circuit
Floor curing function
1)
Single- or 2-stage burner
Modulating burner
BMU (Boiler Management Unit)
Maintained boiler return temperature with bypass pump and mixing valve
Buffer storage tank charging with heat source
Buffer storage tank charging with solar heat
System pump in different applications
Integration in cascade as cascade slave
Heat generation lock with contact H
Protective boiler start-up
Protection against boiler overtemperatures (pump overrun)
Adjustable minimum and maximum limitation of boiler temperature (boiler flow
temperature)
Burner cycling protection by observing a minimum burner running time
Systems
Heating circuits
Heat generation
Protection for the plant