Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Handling 26.03.2001
2.4.1 Overview of end-user parameters
RVA63.242
RVA53.242
Function
Range
Unit
Resolution
Factory
setting
Setting the clock
1 1 Time of day 0...23:59 h / min 1 min 00:00
2 2 Weekday 1...7 Day 1 day 1
3 3 Date (day, month) 01.01...31.12 tt.MM 1 -
4 4 Year 1999...2099 jjjj 1 -
Time switch program 1
5 5 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
6 6 Switch-on time 1
st
period - -:- -...24:00 h / min 10 min 06:00
7 7 Switch-off time 1
st
period - -:- -...24:00 h / min 10 min 22:00
8 8 Switch-on time 2
nd
period - -:- -...24:00 h / min 10 min - -:- -
9 9 Switch-off time 2
nd
period - -:- -...24:00 h / min 10 min - -:- -
10 10 Switch-on time 3
rd
period - -:- -...24:00 h / min 10 min - -:- -
11 11 Switch-off time 3
rd
period - -:- -...24:00 h / min 10 min - -:- -
Time switch program 2
12 12 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
13 13 Switch-on time 1
st
period - -:- -...24:00 h / min 10 min 06:00
14 14 Switch-off time 1
st
period - -:- -...24:00 h / min 10 min 22:00
15 15 Switch-on time 2
nd
period - -:- -...24:00 h / min 10 min - -:- -
16 16 Switch-off time 2
nd
period - -:- -...24:00 h / min 10 min - -:- -
17 17 Switch-on time 3
rd
period - -:- -...24:00 h / min 10 min - -:- -
18 18 Switch-off time 3
rd
period - -:- -...24:00 h / min 10 min - -:- -
Time switch program 3 (d.h.w.)
19 19 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
20 20 Switch-on time 1
st
period - -:- -...24:00 h / min 10 min 06:00
21 21 Switch-off time 1
st
period - -:- -...24:00 h / min 10 min 22:00
22 22 Switch-on time 2
nd
period - -:- -...24:00 h / min 10 min - -:- -
23 23 Switch-off time 2
nd
period - -:- -...24:00 h / min 10 min - -:- -
24 24 Switch-on time 3
rd
period - -:- -...24:00 h / min 10 min - -:- -
25 25 Switch-off time 3
rd
period - -:- -...24:00 h / min 10 min - -:- -
D.h.w.
26 26 Nominal setpoint of d.h.w. temperature (TBWw)
TBWRw Line 120
TBWmax Line 50 (OEM)
TBWR...TBWmax °C 1 55
Heating circuit
27 27 Reduced room temperature setpoint (TRRw)
heating circuits 1 and 2
TRF Frost protection setpoint of the room temperature,
line 28
TRN Setpoint knob heating circuit
TRF...TRN °C 0.5 16
28 28 Room temperature frost protection setpoint (TRFw)
heating circuits 1 and 2
TRRw Line 27
4...TRRw °C 0.5 10