58/64
Building Technologies Division User Manual RWF50... CC1U7866en
Infrastructure & Cities Sector 12 Technical data 25.07.2014
12.7 Environmental conditions
Storage
DIN IEC 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -40...70 °C
Humidity <95% r.h.
Transport
DIN IEC 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -40...70 °C
Humidity <95% r.h.
Operation
DIN IEC 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range
-20...50 °C
Humidity <95% r.h.
Installation altitude Max. 2,000 m above sea level
Attention!
Condensation, formation of ice and ingress of water are not permitted!
12.8 Segment display
Height of numerals
- Upper display 10 mm
- Lower display 7 mm
Color
- Upper display Red
- Lower display Green
Digits 4 (including 0, 1 or 2 decimal places,
configurable)
Range of display -1999...9999
12.9 Standards and certificates
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Low-voltage directive, to DIN EN 60730-1
2004/108/EC
2006/95/EC
ISO 9001: 2008
Cert. 00739
ISO 14001: 2004
Cert. 38233