Description
3.6 C-PLUG
SCALANCE X-300
32 Compact Operating Instructions, 05/2016, A5E00982643-14
LED color
LED status
Meaning
yellow flashes / lit Receiving data at port.
With SCALANCE X-300 devices, both the receipt and the
sending of data is indicated for the optical gigabit ports.
Meaning in display mode B
LED color
LED status
Meaning
-
off
Port operating at 10 Mbps.
green
on
Port operating at 100 Mbps.
orange
on
Port operating at 1000 Mbps.
If there is a problem on the connection and the type of transmission is fixed (autonegotiation
off), the desired status, in other words the set transmission speed (1000 Mbps, 100 Mbps, 10
Mbps) continues to be displayed. If there is a problem on the connection and autonegotiation
is active, the port LED goes off.
Meaning in display mode C
LED color
LED status
Meaning
-
off
Port operating in half duplex.
green
on
Port operating in full duplex.
Meaning in display mode D
LED color
LED status
Meaning
- off The port is not monitored; in other words, if a link is not
established at the port, this does not trigger the signaling
contact.
green on The port is monitored, in other words, if no connection
was established at the port (for example no cable insert-
ed), this triggers the signaling contact and an error state
results.
3.6
C-PLUG
3.6.1
Area of application and function of the C-PLUG
Area of application
The C-PLUG (configuration plug) that ships with the product is an exchangeable memory
medium for storing the configuration data of the device. The device can also be operated
without a C-PLUG.
This allows fast and uncomplicated replacement of a device. The C-PLUG is taken from the
previous device and inserted in the new device. The first time it is started up, the

Table of Contents