Parameter assignment
7.2 Parameterizing via the operator interface
74
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
Selection
Range
Factory setting
DAYL.SAVING Automatic time change.
OFF:
Time change is switched off.
AUTO EU:
Time change within the European Union
The internal clock is put forward from 1 a.m.
UTC to 2 a.m. UTC on the last Sunday in
March.
Changeover to standard time: The internal
clock is put back from 2 a.m. UTC to 1 a.m.
UTC on the last Sunday in October.
AUTO US:
Time change within the USA
The internal clock is put forward from 2 a.m.
local time to 3 a.m. on the second Sunday in
March.
Changeover to standard time: The internal
clock is put back from 2 a.m. local time to 1
a.m. on the first Sunday in November.
TABLE:
Time change can be individually parameter-
ized.
The parameters can be set in the software.
AUTO EU
SNTP
(applies only to PAC3220)
Protocol is used for transmitting the time and for
synchronization.
OFF:
SNTP function deactivated.
ACTIVE:
The device automatically requests the time
from the NTP server.
BCST Client:
The device receives time frames which are
sent from an NTP server.
OFF
IP
(only when SNTP is activat-
ed)
(applies only to PAC3220)
If an SNTP IP address is configured, only data
from this IP address is accepted.
0.0.0.0
0.0.0.0